PROTECTIVE FUNCTIONS

5.3.4 Insulation resistance test using megger

1)Before performing the insulation resistance test using a megger on the external circuit, disconnect the cables from all terminals of the inverter so that the test voltage is not applied to the inverter.

2)For the continuity test of the control circuit, use a tester (high resistance range) and do not use the megger or buzzer.

3)For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test on the control circuit. (Use a 500VDC megger.)

 

R<L1> Inverter

U

 

 

 

Motor

Power

 

 

 

IM

S<L2>

V

 

 

 

supply

 

 

 

T<L3>

M

 

 

 

 

 

 

 

 

 

DC500V megger

Ground terminal

5.3.5 Dielectric strength test

Do not conduct a dielectric strength test. The inverter's main circuit uses semiconductors, which may be deteriorated if a pressure test is made.

Daily and Periodic Inspection

Area of

Inspection

 

 

Interval

 

 

 

 

 

 

Periodic

 

 

 

Inspec-

Description

 

Method

Criterion

Instrument

Item

Daily

 

 

tion

 

1

2

 

 

 

 

 

 

 

year

years

 

 

 

 

 

 

 

 

 

 

Ambient

 

 

 

 

 

 

 

 

temperature:

 

 

Surrounding

Check ambient

 

 

 

 

10° C to +40° C,

Thermometer,

 

temperature, humidity,

{

 

 

(Refer to page 3)

non-freezing.

hygrometer,

 

environment

dust, dirt, etc.

 

 

 

 

Ambient humidity:

recorder

 

 

 

 

 

 

 

90% or less,

 

General

 

 

 

 

 

 

non-condensing.

 

 

 

 

 

 

 

 

 

 

Overall unit

Check for unusual

{

 

 

Visual and auditory

No fault.

 

 

vibration and noise.

 

 

checks.

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

Measure voltage

Within permissible

 

 

 

 

 

 

AC voltage

 

 

Check that main circuit

 

 

 

across inverter

Tester, digital

 

supply

{

 

 

fluctuation

 

voltage is normal.

 

 

terminals R-S-T

multimeter

 

voltage

 

 

 

(Refer to page 40)

 

 

 

 

 

 

<L1-L2-L3,>.

 

 

 

 

(1) Check with megger

 

{

{

(1) Disconnect all

(1) 5M or more.

 

 

 

(across main circuit

 

 

 

cables from

(2), (3) No fault.

 

 

 

terminals and

 

 

 

inverter and

 

 

 

 

ground terminal).

 

 

 

measure across

 

 

 

 

(2) Check for loose

 

{

 

terminals R, S, T,

 

500VDC class

 

General

screws and bolts.

 

 

 

U, V, W <L1, L2,

 

 

(3) Check for

 

{

 

L3, U, V, W>, and

 

megger

 

 

 

 

 

 

 

overheat-ing of

 

 

 

ground terminal

 

 

Main

 

each part.

 

 

 

with megger.

 

 

 

(4) Clean.

 

 

 

(2) Re-tighten.

 

 

circuit

 

 

 

 

 

 

 

 

 

 

 

(3) Visual check.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) Check conductors

 

{

 

(1), (2) Visual check.

(1), (2) No fault.

 

 

Conductors,

for distortion.

 

 

 

 

 

 

 

(2) Check cable

 

{

 

 

 

 

 

cables

sheaths for

 

 

 

 

 

 

 

 

breakage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal

Check for damage.

 

{

 

Visual check.

No fault

 

 

block

 

 

 

 

 

 

 

 

 

 

 

35

Page 46
Image 46
Mitsubishi Electronics FR-A500L instruction manual Insulation resistance test using megger, Dielectric strength test