5.1Errors (Alarms)

PROTECTIVE FUNCTIONS

If any fault has occurred in the inverter, the corresponding protective function is activated and the error (alarm) indication appears automatically on the PU display. When the protective function is activated, refer to "5.2 Troubleshooting" and clear up the cause by taking proper action. If an alarm stop has occurred, the inverter must be reset to restart it.

5.1.1

Error (alarm) definitions

 

 

 

 

 

 

 

 

 

Operatio

 

Paramete

 

 

 

 

n Panel

 

 

 

 

 

 

r Unit

Name

Description

Display

 

 

(FR-PU04)

 

 

 

 

(FR-DU04)

 

 

 

 

 

 

 

 

 

E.OC1

 

OC During

During

 

 

 

 

Acc

acceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stedy Spd

During

 

When the inverter output current reaches or exceeds approx. 200% of

E.OC2

 

constant

Overcurrent

 

OC

the rated current, the protective circuit is activated to stop the inverter

 

 

speed

shut-off

 

 

 

 

output.

 

 

 

OC During

During

 

 

 

 

 

 

 

E.OC3

 

deceleration

 

 

 

 

 

Dec

During stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E.OV1

 

OV During

During

 

 

 

 

Acc

acceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

If regenerative energy from the running motor causes the inverter's

 

 

Stedy Spd

During

 

 

 

Regenerative

internal main circuit DC voltage to reach or exceed the specified value,

E.OV2

 

constant

 

OV

overvoltage

the protective circuit is activated to stop the inverter output.

 

 

speed

 

 

 

 

shut-off

This may also be activated by a surge voltage generated in the power

 

 

 

During

 

 

OV During

 

supply system.

 

E.OV3

 

deceleration

 

 

 

 

 

 

 

 

Dec

During stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The electronic overcurrent protection in the inverter detects motor

 

 

 

 

 

overheat due to overload or cooling capability reduced during constant-

 

 

 

 

 

speed operation. When 85% of the preset value is reached, pre-alarm

E.THM

 

Motor

 

Motor

(TH indication) occurs. When the specified value is reached, the

 

Ovrload

 

protective circuit is activated to stop the inverter output. When a special

 

 

Overload

 

 

 

 

 

motor such as a multi-pole motor or more than one motor is run, the

 

 

 

shut-off

 

motor cannot be protected by the electronic overcurrent protection.

 

 

 

(electronic

 

Provide a thermal relay in the inverter output circuit.

 

 

 

overcurrent

 

 

 

 

 

 

protection)

 

If a current not less than 150% of the rated output current flows and

 

 

 

 

 

 

 

Inv.

 

 

overcurrent shut-off (OC) does not occur (200% or less), inverse-time

E.THT

 

 

Inverter

characteristics cause the electronic

overcurrent protection to be

 

Overload

 

 

 

 

 

activated to stop the inverter output. (Overload immunity: 150%, 60 sec)

 

 

 

 

 

 

 

 

 

 

At low-speed regions, the operation time may be short.

 

 

 

 

 

 

 

 

 

 

 

If a power failure has occurred in excess of 15msec (this applies also

 

 

 

 

 

to inverter input shut-off), this function is activated to stop the inverter

 

 

 

 

 

output to prevent the control circuit from misoperation. At this time, the

 

 

Inst.Pwr.

Instantaneous power failure

alarm output contacts are opened (across B-C) and closed (across A-

E.IPF

 

C).

 

 

Loss

protection

 

 

 

 

 

(Note 1) If a power failure persists for more than 100ms, the alarm

 

 

 

 

 

 

 

 

 

 

output is not provided, and if the start signal is on at the time of power

 

 

 

 

 

restoration, the inverter will restart. (If a power failure is instantaneous

 

 

 

 

 

within 15msec, the control circuit operates properly.)

 

 

 

 

 

If the inverter power supply voltage drops, the control circuit will not

 

 

 

 

 

operate properly. Furthermore, the motor torque could drop and the heat

 

 

Under

 

 

generated may increase. The inverter

output will be stopped if the

E.UVT

 

Undervoltage protection

power supply voltage drops to 150V (approx. 300V for 400V class) or

 

Voltage

 

 

 

 

less.

 

 

 

 

 

 

 

 

 

 

 

 

The undervoltage protection function will activate if the DC reactor

 

 

 

 

 

accessory is not used.

 

 

 

 

 

 

 

E.FIN

 

H/Sink

Fin overheat

 

If the cooling fin overheats, the temperature sensor is activated to stop

 

O/Temp

 

the inverter output.

 

 

 

 

 

 

 

 

 

 

 

 

 