PROTECTIVE FUNCTIONS

Measuring Points and Instruments

 

 

 

 

 

 

 

 

 

 

Remarks

 

 

 

Item

 

 

Measuring Point

Measuring Instrument

(Reference Measured Value)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply voltage

Across R-S, S-T and T-R

 

Commercial power supply

 

 

 

Moving-iron type AC voltmeter

Within permissible

AC

voltage

V1

 

<Across L1-L2, L2-L3and L3-L1>

 

 

fluctuationRefer to Page 40

 

 

 

 

 

 

 

Power supply side

R, S and T line currents

Moving-iron type AC ammeter

 

 

 

 

 

 

 

 

 

 

 

 

current I1

 

<L1, L2, and L3 line currents>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At R, S and T, and across R-S,

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply side

S-T and T-R

Electrodynamic type single-

P1 = W11 + W12 + W13

 

 

 

 

 

power P1

 

<At L1, L2 and L3, and across

phase wattmeter

(3-wattmeter method)

 

 

 

 

 

 

 

L1-L2, L2-L3and L3-L1>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Calculate after measuring power supply voltage, power supply side current and power supply side

 

Power supply side

power.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power factor Pf 1

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pf1 =

3 V 1

 

× 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier type AC voltmeter

Difference between phases is

 

Output side voltage V2

Across U-V, V-Wand W-U

(Note 1) (Not moving-iron

within ±1% of maximum output

 

 

 

 

 

 

 

type)

voltage.

 

 

 

 

 

 

 

 

 

 

 

 

Current should be equal to or less

Output side current I2

U, V and W line currents

Moving-iron type AC ammeter

than rated inverter current.

 

 

 

Difference between phases is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10% or lower.

 

 

 

 

 

 

 

At U, V and W, and across U-V

Electrodynamic type single-

P2 = W21 + W22

 

 

 

 

 

Output side power P2

2-wattmeter method (or 3-

 

 

 

and V-W

 

 

phase wattmeter

 

 

 

 

 

 

 

wattmeter method)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output side power

Calculate in similar manner to power supply side power factor.

 

 

 

 

 

 

 

 

 

 

 

 

 

P2

 

 

 

 

 

 

 

 

 

 

 

 

 

factor Pf 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pf2 =

3 V 2

 

× 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER lamp lit

 

 

 

 

 

Converter output

 

Across P-N< Across + and - >

Moving-coil type (such as

1.35 × V1

 

 

 

 

 

 

tester)

Maximum 760V during

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

regenerative operation

 

 

 

 

 

Across 2 (+) 5

 

0 to 5V/0 to 10VDC

 

 

 

“5”is common.

Frequency

setting

Across 10 (+) 5

 

5VDC

 

 

 

Frequency setting signal

Across 1 (+) 5

 

0 to ±5V/0 to ±10VDC

 

 

 

 

 

 

 

Across 4 (+) 5

 

4 to 20mADC

 

 

 

 

 

power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across 10E (+) 5

 

10VDC

 

 

 

 

 

 

 

 

 

 

 

 

Approximately. 5VDC at

 

 

 

 

 

 

 

 

 

 

maximum frequency

 

 

 

 

 

 

 

 

 

 

 

 

(without frequency meter)

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC8V

 

 

 

 

 

 

 

 

 

 

 

Across FM (+) SD

Moving-coil type (Tester, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency meter signal

 

 

 

 

may be used) (Internal

 

 

 

T2

 

 

 

 

common.

 

 

 

 

resistance: 50kΩ or larger)

Pulse cycle T2: Set by Pr.55

 

 

 

 

 

 

 

 

Pulse width T1:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjusted by Pr.900

 

 

 

 

 

 

 

 

 

 

 

 

(Valid for

 

 

 

 

is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SD

 

 

 

 

 

 

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

monitoring only)

 

 

 

 

 

 

 

 

 

 

Approximately 10DVC at

 

 

 

 

 

Across AM (+) 5

 

maximum frequency

 

 

 

 

 

 

 

 

 

 

 

 

(without frequency meter)

 

 

 

Start signal

 

Across STF, STR, RH, RM, RL,

 

 

 

 

 

 

 

 

 

 

 

 

 

Select signal

 

RT, AU, STOP, CS (+) SD

 

20 to 30VDC when open.

 

 

 

Reset

 

Across RES (+) SD

 

ON voltage: 1V or less

 

 

 

Output stop

 

Across MRS (+) SD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continuity check (Note 2)

 

 

 

 

 

Across A-C

Moving-coil type

 

 

 

<At OFF>

<At ON>

 

Alarm signal

 

Across A-C: Discontinuity Continuity

 

Across B-C

(such as tester)

 

 

Across B-C: Continuity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discontinuity

 

 

 

Note 1. Accurate data will not be obtained by a tester.

 

 

 

 

 

 

 

 

 

 

 

 

 

2.When Pr. 195 "A, B, C terminal function selection" setting is positive logic.