6 Configuration

Configuration

MIM and Mitsubishi ALPHA XL

 

 

6 Configuration

6.1MIM and Mitsubishi ALPHA XL

Configuration of the Industrial Modems is done via the Mitsubishi Alpha Programming Software (SW0D5-ALVLS-EUL). Detailed information on selecting the modem and setting parameters is to be found within the Mitsubishi Alpha XL manuals at http://www.mitsubishi-automation.com

Alpha XL - Communication Manual

Art. No. 146564

Alpha Software - Software Manual

Art. No. 126017

This AT init string is to be used when connecting an "Alpha XL" to the "MIM-G01":

ATE0S0=2&S0;+IFC=0,0;+CMEE=1;+IPR=9600;+CICB=0;&W

This AT init string is to be used when connecting an "Alpha XL" to the "MIM-A01":

ATE0S0=2Q1+D0\Q0\J0&W

The following chapters will show the most important settings.

6.1.1Project Settings

Load the PLC project into the Alpha Programming Software and adjust some basic settings. Therefore, in the menu bar click

Options > GSM and serial communication

Fig. 6-1:

GSM and serial communication

 

 

 

 

 

In the area Modem, select either GSM (for MIM-G01) or Modem (MIM-A01) and choose the

 

 

 

 

 

name of the modem in use from the list provided on the right (see figure above).

 

 

 

 

 

 

 

 

 

NOTE

 

 

 

If this modem type is not present within the list, you may add it by yourself; detailed informa-

 

 

 

 

 

 

 

 

 

 

tion on that is to be found within chapter 6.1.3.

 

 

 

 

 

If you use a MIM-A01 Modem, click on OK to exit configuration.

 

 

 

 

 

If you use a MIM-G01 Modem, enter the SIM PIN into the appropriate input field and enable the

 

 

 

 

 

„Remote Access“ checkbox, in case you want to remotely access the PLC. The Data format

 

 

 

 

 

should be 8 bits, no parity and 1 stop bit (8N1) with a speed of 9600 baud. Click on OK to exit con-

 

 

 

 

 

figuration.