Monessen Hearth HBDV300N/PSC7 Venting Installation, Step, HBDV7 Series Direct Vent Gas Fireplace

Models: HBDV300N/PV7 HBDV400N/PSC7 HBDV300N/PSC7 HBDV400N/PV7

1 64
Download 64 pages 47.51 Kb
Page 19
Image 19
VENTING INSTALLATION

VENTING INSTALLATION

HBDV7 Series Direct Vent Gas Fireplace

Vertical Sidewall Installation - Twist Lock Pipe

Step 1

Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole lo- cation. Depending on whether the wall is combustible or noncombustible, cut opening to size. Figure 28 (For com- bustible walls first frame in opening.)

NOTE: When using flex vent, the opening will have to be measured according to the 1/2” (13 mm) rise in 12” (305 mm) vent run.

Combustible Walls: Cut a 9B\,”H x 9B\,”W (244 x 244 mm) hole through the exterior wall and frame as shown. Figure 28

Noncombustible Walls: Hole opening must be 7Z\x” (191 mm) in diameter.

Vent Opening for Combustible Walls

9B\,

(244 mm) Min.

9B\,

(244 mm)

Min.

Fireplace Hearth

Framing Detail

Opening for Noncombustible Wall

 

7Z\x

 

 

 

 

 

 

 

(190 mm)

 

 

 

 

 

 

 

 

 

 

FP2293

 

 

 

 

 

 

 

Figure 28 -

 

Fireplace Hearth

 

 

Locate vent opening on wall.

Step 2

Secure firestop to the inside frame, center in the 9B\," x 9B\," vent opening.

Step 3

Place fireplace into position. Measure the vertical height

(X)required from the base of the flue collars to the center of the wall opening. Figure 29

Step 4

Using appropriate length of pipe section(s) attach to fire- place with three (3) screws. Follow with the installation of the inner and outer elbow, again secure joints with three

(3) sheet metal screws.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1181

Figure 29 -

Vertical Height Requirements

Step 5

Measure the horizontal length requirement including a 2” (51 mm) overlap, i.e. from the elbow to the outside wall face plus 2” (51 mm) (or the distance required if installing a second 90° elbow). Figure 30

Always install horizontal venting on a level plane.

Step 6

Use appropriate length of pipe sections - telescopic or fixed - and install. The sections which go through the wall are packaged with the starter kit, and can be cut to suit if necessary.

Sealing vent pipe and firestop gaps with high tem- perature sealant will restrict cold air being drawn in around fireplace.

X

X

Figure 30 -

FP1182

Horizontal Length Requirements

 

54D8000

19

Page 19
Image 19
Monessen Hearth HBDV300N/PSC7, HBDV300N/PV7 Venting Installation, Vertical Sidewall Installation - Twist Lock Pipe, Step