SIGNATURE COMMAND - CHECK GAS PRESSURE and ELECTRICALHBDV7 SeriesINSTALLATIONDirect Vent Gas Fireplace
1.Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance. Contact your dealer immediately.
2.To ease installation, a 24" (610 mm) flex line with manual
3.After completing gas line connection, purge air from gas line and test all gas joints from the gas meter to the fireplace for leaks. Use a solution of 50/50 water and soap solution or a gas sniffer.
4.To check gas pressures at valve, turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point. Turn unit to high. Figure 52. After taking pressure reading, be sure and turn captured screw clockwise firmly to reseal. Do not over torque. Check test points for gas leaks.
Electrical Wiring
General
1.This fireplace is equipped with the Signature Control valve which operates on 6 volts. The 6 volt DC adapter plugs into the fireplace junction box A/C power supply. Four (4) “AA” batteries are used for back up during power outages.
2.The Signature Command System can also be operated without A/C power. The system can run on four (4) “AA” batteries for approximately six (6) months under normal use.
3.A/C power must be used to power the A/C module, blowers, lights and AUX accessories if used with this fireplace.
Optional Accessory Requirements
1.This fireplace may be used with a wall switch, wall mounted thermostat and/or Signature Command wire- less controls.
2.The command center control may be mounted on the wall with the use of the SCSWEK 15ft. wall mount exten- sion kit.
Pressure Inlet
Pressure Outlet | Pilot Adjust- | |
ment Screw | ||
| ||
Figure 52 - |
| |
Signature Command Valve |
|
| WARNING | Do not use open flame to check for gas |
|
| |
|
| leaks. |
|
|
|
|
| Electrical connections should only |
|
| be performed by a qualified, licensed |
|
| electrician. Main power must be off when |
| WARNING | connecting to main electrical power supply |
| or performing service. All wiring shall be | |
|
| |
|
| in compliance with all local, city and state |
|
| codes. The appliance, when installed, must |
|
| be electrically grounded in accordance with |
|
| local codes or in the absence of local codes, |
|
| with the National Electrical Code ANSI/NFPA |
|
| 70 (latest edition) and Canadian Electrical |
|
| Code, CSA C22.1. |
|
|
|
|
|
|
| CAUTION | Label all wires before disconnecting when |
|
| |
|
| servicing controls. Wiring errors can cause |
|
| improper and dangerous operation. |
|
|
|
54D8000 | 31 |