VENTING INSTALLATION | HBDV7 Series Direct Vent Gas Fireplace |
10.Add additional vent lengths for proper height. Figure 41
11.Apply high temperature sealant to 4” and 7” collars of vertical vent termination and install.
If there is a room above ceiling level, fire stop spacer must be installed on both the bottom ad the top side of the ceil- ing joists. If an attic is above ceiling level an Attic Insula- tion Shield must be installed. The enlarged ends of the vent section always face downward.
Typical Roof | FP1184 | |
Support | Typical Ceiling | |
Application | ||
Support | ||
| ||
Figure 39 - | Application | |
| ||
Venting Supports |
|
Horizontal Overhang
| 2 ft. |
|
|
| 2 ft. Min. |
|
|
|
| |||||
| Min. |
|
|
|
|
|
|
| ||||||
|
|
|
| Lowest |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| Discharge |
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| Opening |
|
|
| ||||
Termination |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Vent |
|
|
|
|
|
|
|
|
|
|
| 12 |
| |
|
|
|
|
|
|
| H* |
| ||||||
|
|
|
|
|
|
| X |
|
| |||||
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Storm Collar |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| FP1971 | |
Flashing |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1” Minimum Clearance to
Combustibles
Concentric
Vent Pipe
Figure 40 -
Minimum Chimney Clearance
Roof Pitch | H (feet) |
Flat to 6/12 | 1.0 |
Over 6/12 to 7/12 | 1.25 |
Over 7/12 to 8/12 | 1.5 |
Over 8/12 to 9/12 | 2.0 |
Over 9/12 to 10/12 | 2.5 |
Over 10/12 to 11/12 | 3.25 |
Over 11/12 to 12/12 | 4.0 |
|
|
*H - Minimum height from roof to lowest discharge opening of vent
3 #5 Sheet Metal Screws per Joint
Sealant
Storm Collar
TWL101a
Figure 41 -
Roof Flashing
54D8000 | 23 |