VENT INSTALLATION

HBDV7 Series Direct Vent Gas Fireplace

WARNING

Horizontal sections of this vent system require a minimum of 3” clearances to combustibles at the top of the flue and 1” clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1” clearance all around the flue is acceptable at this point of penetration. If vertical rise is 7Z\x” feet or higher when top venting, the clearance to combustibles is 1” on all sides of the horizontal run.

Vertical sections of this vent system require a minimum of 1” clearance to combustibles on all sides of the pipe.

WARNING

This fireplace must be vented to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance must use a separate vent system. Do not use common vent systems.

*3”

**1”

**1”

48”

(1219 mm)***

*3"**1"

**1" 3356 ” (841 mm)***

***296 " (753 mm) for 300 Series

***4456O” (1130 mm) for 300 Series

Figure 16 -

Combustible Clearances for Vent Pipe

FP2095a

*A Minimum 3” Clearance to the Top is Required Along Horizontal Length until Flue Pipe Penetrates Outside Wall

**A Minimum 1” Clearance to Combus- tibles Permitted All Around Flue at Out- side Wall

54D8000

15

Page 15
Image 15
Monessen Hearth HBDV300N/PSC7, HBDV300N/PV7, HBDV400N/PSC7, HBDV400N/PV7 manual Vent Installation, 1219 mm