Monessen Hearth HBDV400N/PV7 manual HBDV7 Series Direct Vent Gas Fireplace, Venting Installation

Models: HBDV300N/PV7 HBDV400N/PSC7 HBDV300N/PSC7 HBDV400N/PV7

1 64
Download 64 pages 47.51 Kb
Page 18
Image 18
AB

HBDV7 Series Direct Vent Gas Fireplace

VENTING INSTALLATION

When installing the appliance as a rear vent unit, the 90° or 45° Transition Elbow attached directly to the rear of the unit is NOT INCLUDED in the following cri- teria and calculations, and unless specifically men- tioned should be ignored when calculating venting layouts.

• The maximum number of 90° elbows per side wall in-

stallation is three (3). Figure 23

The maximum number of elbow degrees in a system is 270°. Figure 27

Example:

Elbow 1

= 90°

 

 

Elbow 2

= 45°

 

 

Elbow 3

= 45°

 

 

Elbow 4

= 90°

Total angular variation

= 270°

• If a 90° elbow is fitted directly on top of the fireplace

flange the maximum horizontal vent run before the ter-

mination or a vertical rise is 36” (914 mm). Figure 24

• If a 90° elbow is used in the horizontal vent run (level

height maintained) the horizontal vent length is re-

duced by 36” (914 mm). Figures 24 & 25. This does

not apply if the 90° elbows are used to increase or

redirect a vertical rise. Figure 23

3 x 90°

3 x 90°

Elbows

Elbows

Figure 23 -

FP1176

Figure 25 -

Horizontal Run

Reduction

AB

A + B = 17' (Max.)

(5.2m)

7'6"

(2.3m)

FP1177

B

7’

(2.1 m)

Maximum three (3) 90° elbows per installation

36"

36"

(914 mm)

(914 mm)

Max.

Max.

 

FP1177

Figure 24 -

Maximum horizontal run with no rise

Example: According to the vent graph (Page 14) the maximum horizontal vent length in a system with a 7Z\x’ (2.3 m) rise is 20’ (6 m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17’ (5.2 m).

In Figures 26 & 27, dimension A plus B must not be great- er than 17’ (5.2 m)

The maximum number of 45° elbows permitted per in- stallation is six (6). These elbows can be installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (457 mm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

A 10’ (3 m)

7’6"

(2.3 m)

Figure 26 -

Maximum Vent Run with Elbows

V584-201

 

1+ 2 + 3 + 4 = 270°

 

1

1

 

2

2

 

3

3

 

4

4

 

Figure 27 -

FP1180

 

Maximum Elbow Usage

 

18

54D8000

Page 18
Image 18
Monessen Hearth HBDV400N/PV7 HBDV7 Series Direct Vent Gas Fireplace, Venting Installation, AB A + B = 17 Max 5.2m 76 2.3m