KHLDV Series Gas Fireplace

If the foundation

 

 

is recessed, use

 

 

recess brackets

 

Snorkel

(not supplied)

 

 

 

for securing

Foundation

 

lower portion

 

Recess

 

of the snorkel.

 

 

Wall

Fasten brack-

 

 

Screws

ets to wall first,

 

 

 

then secure to

Watertight Seal

 

snorkel with

Sheet

self drilling #8 x

Around Pipe

Metal

1/2 sheet metal

 

Screws

screws. It will

 

 

be necessary Figure 20 -

 

to extend vent Snorkel Installation, Recessed Foundation

pipes out as far

 

 

as the protruding wall face. Figure 20

 

WARNING

 

soil.

 

• Do not back fill around snorkel.

 

A clearance of at least 4" must be

 

 

maintained between the snorkel and the

 

 

 

vertical through-the-roof applica- tions

NOTICE

A restrictor disc must be installed on

 

 

vertical terminations that are higher than

 

12' (366 cm).

 

 

Install restrictor disc as shown in Figure 21 for vertically vented applications.

Up to two (2) restrictor discs may be needed for 40' instal- lation.

The two (2) restrictor discs suppled will work for most instal- lations. If a third disc is needed order Part No. 56D3027.

This gas fireplace has been approved for,

Vertical installations up to 40' (12 m) in height. Up to a 10' (3 m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. Figure 22

NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration. Unless the vertical run is 7Z\x feet or higher form floor of fireplace, the clearance for the horizontal run is 1" on all sides.

ventNG installation

Restrictor

Disc

Figure 21 -

Install Restrictor Disc into

Fireplace Collar

Fireplace

Collar

FP2703

40' Maximum Height

12' Minimum Height

10'

Maximum

24" Min.

Support Straps

Every 3'

FP1183

Figure 22 -

Support Straps for Horizontal Runs

Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.

Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be reduced by 18" (450 mm).

Example: Maximum horizontal length

No elbows

=

10’ (3 m)

1x45° elbows

=

8.5’ (2.6 m)

2x45° elbows

=

7’ (2.1 m)

A minimum of an 8' (2.5 m) vertical rise is required.

Two sets of 45°elbows offsets may be used within the vertical sections. From 0 to a maximum of 8' (2.5 m) of vent pipe can be used between elbows. Figure 23

The maximum angular variation allowed in the system is 270°. Figure 23

The minimum height of the vent above the highest point of penetration through the roof is 2' (610 mm).

18

73D0024

Page 18
Image 18