Running state, or has a low start-up torque, DO decrease or increase the PER_CMT_START_US value. Table 6-2shows typical setting examples.

Must be:

PER_CMT_START_US<=PER_CMT_MAX_US/2

NOTE: Setting this constant is an empirical process. It is difficult to use a precise formula, because there are many factors involved which are difficult to obtain in the case of a real drive (motor and load mechanical inertia, motor electromechanical constants, and sometimes also the motor load). So they need to be set with a specific motor.

PER_CMT_START_US can be evaluated with PC master software tuning file tuning_bldc.pmp.

Table 6-2. Start-up Period

 

Typical

First-to-Seco

Second-to-Thi

 

nd

rd

Motor Size

PER_CMT_START_

Commutation

Commutation

 

US

 

Step Period

Step Period

 

 

 

 

 

 

 

 

Slow motor/high load and

8000.0

s

8 ms

8–16 ms

motor mechanical inertia

 

 

 

 

 

 

 

 

 

Fast motor/high load and

2000.0

s

2 ms

2–4 ms

motor mechanical inertia

 

 

 

 

 

 

 

 

 

Maximal commutation period limit [s]:

/* CAN_CHANGE_6_EXPER: */ #define PER_CMT_MAX_US 65536.0

Range: <0,65535*UNIT_PERIOD_T2_US>

Usually it is not recommended to change PER_CMT_MAX_US. The change is only necessary if the commutation period at start-up is to long.

Alignment to Start Increment of the regulators output [-]:

/* CAN_CHANGE_7_EXPER: */ #define START_INCR_OOUTREG 20.0

Range: <-128,127>

Designer Reference Manual

 

DRM028 — Rev 0

 

 

 

146