REAR EXIT / HORIZONTAL TERMINATION

12

REAR EXIT / HORIZONTAL TERMINATION

(HT) < (VT)

Example 4:

90°

 

H3

 

 

Simple venting configuration

 

V2

(only two 90° elbows)

 

H2

V190°

H1

FIGURE 13

 

90°

FIGURE 12

See graph to determine the required vertical rise VT for the required horizontal run HT

35

33.3Example 4:

30 H2

REQUIRED

VERTICAL

20

RISE IN 17.5

FEET VT

10

0 .5

2.5

5

7.5

10

12.5

15

17.5

20

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

V1

 

=9 ft

V2

 

=6 ft

VT

 

= V1 + V2 = 9 + 6 = 15 ft

H1

 

=3 ft

H2

 

=2 ft

H3

 

=1.5 ft

HR

 

= H1 + H2 + H3 = 3 + 2 + 1.5 = 6.5 ft

HO

 

= .03(four 90° elbows - 90°)

 

 

= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft

HT

+ VT

=HR + HO = 6.5 + 8.1 = 14.6 ft

HT

=14.6 + 15 = 29.6 ft

Formula 1: HT < VT 14.6 < 15

Formula 2: HT + VT < 35 feet 29.6 < 35

Since both formulas are met, this vent configuration is acceptable.

For vent configurations requiring more than two 90° elbows the following formulas apply:

Formula 1: HT < VT

Formula 2: HT + VT < 35 feet

W415-0612 / C / 01.25.08

Page 12
Image 12
Napoleon Fireplaces GD19P, GD19N manual Rear Exit / Horizontal Termination, H2, Ht Vt