DEFINITIONS

10

DEFINITIONS

For the following symbols used in the venting calculations and examples are:

>- greater than

>- equal to or greater than < - less than

< - equal to or less than

HT - total of both horizontal vent lengths (HR) and offsets (HO) in feet

HR - combined horizontal vent lengths in feet

HO - offset factor: .03(total degrees of offset - 90°*) in feet

VT - combined vertical vent lengths in feet

ELBOW VENT LENGTH VALUES

 

feet

inches

0.03

0.5

15°

0.45

6.0

30°

0.9

11.0

45°

1.35

16.0

90°*

2.7

32.0

*the first 90° offset has a zero value and is shown in the formula as -90°

TOP EXIT / HORIZONTAL TERMINATION

(HT) < (VT)

For vent configurations requiring more than one 90° elbow,

the following formulas apply:

FIGURE 7

Formula 1: H < V

 

Formula 2: HTT+ VTT< 35 feet

Simple venting configuration

 

 

 

 

 

 

 

 

 

90°

H2

 

 

 

 

 

 

 

 

 

 

(only one 90° elbow)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 8

 

 

V2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90°

 

 

 

 

 

 

 

 

 

 

 

 

 

90°

H1

See graph to determine the required vertical rise VT for the

 

 

 

 

V1

 

required horizontal run HT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.3

 

 

 

 

 

 

 

 

Example 1:

 

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

V1

=

3 ft

 

 

 

REQUIRED

 

 

 

 

 

 

 

 

 

 

 

VERTICAL

 

 

 

 

 

 

 

 

V2

=

8 ft

 

 

 

RISE IN 17.5

 

 

 

 

 

 

 

 

VT

= V1 + V2 = 3 + 8 = 11 ft

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FEET VT

 

 

 

 

 

 

 

 

H1

=

2.5 ft

 

 

 

 

 

 

 

 

 

 

H2

=

2 ft

 

 

 

10

 

 

 

 

 

 

 

 

+ H2

 

 

 

 

 

 

 

 

 

 

 

HR

= H1

= 2.5 + 2 = 4.5 ft

 

0 .5

 

 

 

 

 

 

 

 

HO

= .03(three 90° elbows - 90°) = .03(270° - 90°) = 5.4

2.5

5

7.5

10

12.5

15

17.5

20

ft

 

 

 

 

 

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

 

HT

=

HR + HO = 4.5 + 5.4 = 9.9 ft

 

 

HT

+ VT

= 9.9 + 11 = 20.9 ft

 

The shaded area within the lines represents acceptable

 

Formula 1:

HT

< VT

 

values for HT and VT .

 

 

 

 

 

 

 

 

 

9.9 < 11

 

 

 

 

 

 

 

 

 

 

Formula 2:

HT

+ VT < 35 feet

 

 

 

 

 

 

 

 

 

 

 

 

 

20.9 < 35

 

Since both formulas are met, this vent configuration is acceptable.