VENTING APPLICATION FLOW CHART

VENTING APPLICATION FLOW CHART

FIREPLACE VENT EXIT

 

 

REAR EXIT

 

 

 

 

 

TOP EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal Termination

Vertical Termination

Horizontal Termination

Vertical Termination

W415-0612 / C / 01.25.08

Vertical rise is equal to or greater t h a n t h e horizontal run

Horizontal run + verti- cal rise to maximum of 35 feet

Vertical rise is less than horizontal run

Horizontal run + verti- cal rise to maximum of 24.75 feet

3.5times the vertical rise equal to or greater than the horizon- tal run

Vertical rise is equal to or greater than the horizontal run

Horizontal run + verti- cal rise to maximum of 35 feet

Vertical rise is less than horizontal run

Horizontal run + verti- cal rise to maximum of 35 feet

3times the vertical rise equal to or greater than the horizon- tal run

Vertical rise is equal to or greater than the horizontal run

Horizontal run + verti- cal rise to maximum of 35 feet

vertical rise is less than horizontal run

Horizontal run + verti- cal rise to maximum of 24.75 feet

4.2times the vertical rise equal to or greater than the horizon- tal run

Vertical rise is equal to or greater than the horizontal run

Horizontal run + verti- cal rise to maximum of 35 feet

Vertical rise is less than horizontal run

Horizontal run + verti- cal rise to maximum of 35 feet

3 times the vertical rise equal to or greater than the horizon- tal run