TYPICAL VENT INSTALLATIONS

7

TYPICAL VENT INSTALLATIONS

FIGURE 2a

FIGURE 2b

REAR EXIT

16”

MINIMUM

35 FT MAXIMUM

3 FT MINIMUM

20" MAXIMUM

26 3/8" MINIMUM PLUS RISE*

TOP EXIT

FIGURE 3a

16”

MINIMUM

35 FT MAXIMUM

3 FT MINIMUM

 

 

24" MAXIMUM

FIGURE 3b

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10"

MINIMUM

43 1/8" MINIMUM PLUS RISE*

33 1/8"

* Refer to "Venting"

section.

SPECIAL VENT INSTALLATIONS

PERISCOPE TERMINATION

Use the GD201 periscope kit to locate the air termination above grade. The periscope must be installed so that when final grading is completed, the bottom air slot is located a minimum of 12" above grade. The maximum allowable vent length is 10 ft.

FIGURE 4a

 

FIGURE 4b

 

12”

12”

 

MINIMUM

 

MINIMUM

 

 

24”

 

 

MINIMUM

24”

 

 

MINIMUM

 

CORNER TERMINATION

The maximum vent length for a corner installation is 20" of horizontal run, in addition to the 45° offset. In this case zero rise is acceptable when using rigid. See FIGURE 5a. Flexible venting must maintain a 6" rise. See FIGURE 5b.

FIGURE 5a

 

 

FIGURE 5b

 

 

20” MAXIMUM

 

 

6” RISE

 

 

 

 

 

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAXIMUM 10FT VENT LENGTH

TOP EXIT INSTALLATION

REAR EXIT INSTALLATION