Napoleon Fireplaces GDS60N manual Ht Vt, for the, required horizontal run HT, Vertical, Rise In

Models: GDS60N

1 52
Download 52 pages 27.89 Kb
Page 20
Image 20
for the

20

(HT) > (VT)

Simple venting configuration

See graph to determine the required vertical rise VT

for the

(only two 90° elbows)

required horizontal run HT.

 

 

 

 

REQUIRED

 

VERTICAL

 

RISE IN

FIGURE 3.10c

INCHES VT

 

147

150

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

66

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

0

2.5

5

7.5

10

12.5

15

17.5

20

 

1

 

3.5

 

 

 

 

 

19.25

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

 

 

 

 

 

 

 

 

 

The shaded area within the lines represents acceptable

 

 

 

 

 

 

 

 

 

 

 

 

 

values for HT and HT

 

 

 

 

 

 

 

 

 

90°

 

 

For vent configurations requiring more than two 90° elbows, the following formulas apply:

Formula 1: HT

< 3.5VT

 

 

 

 

 

 

 

 

 

 

 

 

H3

Formula 2: HT

+ VT < 24.75 feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example 4:

 

 

 

 

90°

V2

V1

= 4 FT

 

 

 

 

 

 

 

 

 

V2

= 1.5 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

H2

 

 

 

 

 

 

 

 

 

 

 

 

 

VT

= V1

+ V2 = 4 + 1.5 = 5.5 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

H1

= 2 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H2

= 1 FT

 

 

 

 

 

 

 

 

 

 

 

 

90°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1

 

 

 

H3

= 1 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H4

= 1.5 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

R

= H

1

+ H

+ H

+ H = 2 + 1 + 1 + 1.5 = 5.5 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

HO

= .03 (four 90° elbows + one 45° elbow - 90°)

 

 

 

 

H1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

= .03 (90 + 90 + 90 + 90 + 45 - 90) = 9.45 FT

 

 

 

 

 

 

 

 

90°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HT

= HR

+ HO

= 5.5 + 9.45 = 14.95 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HT

+ VT

= 14.95 + 5.5 = 20.45 FT

 

 

 

 

 

 

 

 

FIGURE 3.10d

Formula 1:

 

 

HT

< 3.5VT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5VT = 3.5 x 5.5 = 19.25 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14.95 < 19.25

 

 

 

 

 

 

 

 

 

 

 

 

 

Formula 2:

 

 

HT

+ VT < 24.75 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20.45 < 24.75

 

 

 

 

 

 

 

 

 

 

 

 

 

Since both formulas are met, this vent configuration is acceptable.

16.3_2

W415-0788 / A / 09.22.09

Page 20
Image 20
Napoleon Fireplaces GDS60N manual Ht Vt, for the, required horizontal run HT, Vertical, Rise In, Inches Vt