Napoleon Fireplaces GDS60N manual 5.6OPTIONAL WALL SWITCH / THERMOSTAT, Single Wall Or “B” Vent

Models: GDS60N

1 52
Download 52 pages 27.89 Kb
Page 30
Image 30
5.6OPTIONAL WALL SWITCH / THERMOSTAT

30

Installation and servicing to be done by a qualified installer. Do not use open flame.

5.5.1

5.5.2

Move the appliance into position and secure.

If equipped with a flex connector the appliance is designed to accept a 1/2” gas supply. Without the connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off valve to turn off the gas supply to the appliance.

5.5.3 Connect the gas supply in accordance to local codes. In the absence of local codes, install to the current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States.

5.5.4 When flexing any gas line, support the gas valve so that the lines are not bent or kinked. 5.5.5 Check for gas leaks by brushing on a soap and water solution.

30.1

5.6OPTIONAL WALL SWITCH / THERMOSTAT

For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient location. Route 2 strand solid core millivolt wire from the gas appliance to the wall switch / millivolt thermostat. The recommended maximum lead length depends on the wire size:

WIRE SIZE

MAX. LENGTH

14 gauge

100 feet

16 gauge

60 feet

18 gauge

40 feet

DIRECT VENT MODEL GDS60: Disconnect one of the wire leads to the on/off switch then connect the wire leads from the optional thermostat / wall switch / remote. See "WIRING DIAGRAM" section.

B-VENT MODEL GS60: Disconnect one of the wire leads to the on/off switch then connect the wire leads from the optional thermostat / wall switch / remote / spill switch to "B" vent adaptor. See "WIRING DIAGRAM" sec- tion.

5.7B-VENT SPECIFICS - MODEL GS60 5.7.1 CHIMNEY INSTALLATION

!WARNING

A CHIMNEY VENTING THIS APPLIANCE SHALL NOT VENT ANY SOLID FUEL BURNING APPLIANCE.

FIGURE 5.7.1a

“A” VENT - SOLID FUEL WOOD BURNING CHIMNEY & VENT CONNECTOR

 (LINER NEEDED IF INSIDE DIAMETER IS 6” OR LARGER)SINGLE WALLMASONRY CLAY LINED (LINER NEEDED IF INSIDE DIAMETER IS 6” OR LARGER)

SINGLE WALL

OR “B” VENT

MASONRY CLAY LINED

CHIMNEY + VENT

CONNECTOR

FIGURE 5.7.1b

(NO NEW LINER

NEEDED IF OLD

LINER DIAMETER (NO NEW LINER IS 4-5”)

“B” VENT LIQUID FUEL GAS BURNING CHIMNEYManual background SINGLE WALL OR “B” VENT

“B” VENT LIQUID FUEL GAS BURNING CHIMNEY

FIGURE 5.7.1c

W415-0788 / A / 09.22.09

Page 30
Image 30
Napoleon Fireplaces GDS60N manual 5.6OPTIONAL WALL SWITCH / THERMOSTAT, LINER NEEDED IF INSIDE DIAMETER IS 6” OR LARGER