3.3SPECIAL VENT INSTALLATIONS 3.3.1 PERISCOPE TERMINATION

Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when final grading is completed, the bottom air slot is located a minimum 12” above grade. The maximum allowable vent length is 10’.

12" MIN. TO

GRADE

12" MIN.

TO GRADE

24" MINIMUM

FIGURE 3.3.1a

29" MINIMUM

30 1/2"

FIGURE 3.3.1b

9.4

3.3.2 CORNER TERMINATION

The maximum vent length for a corner installation is 24".

24”

MAXIMUM

 

RISE

0”

 

FIGURE 3.3.2

CORNER INSTALLATION