Napoleon Fireplaces GDS60N manual 3.8TOP EXIT HORIZONTAL TERMINATION, Ht Vt

Models: GDS60N

1 52
Download 52 pages 27.89 Kb
Page 17
Image 17
3.8TOP EXIT HORIZONTAL TERMINATION

17

3.8TOP EXIT HORIZONTAL TERMINATION

(HT) > (VT)

Simple venting configuration (only one 90° elbow)

See graph to determine the required vertical rise VT for the

required horizontal run HT.

147”

150

FIGURE 3.8a

REQUIRED

100

 

 

 

 

 

 

 

 

 

VERTICAL

 

 

 

 

 

RISE IN

 

 

 

 

 

INCHES VT

57”

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

19 1/2”

 

 

 

 

 

0

5

10

15

20

 

 

2’

 

12.5’

19.5’

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

 

 

 

 

 

 

 

 

 

The shaded area within the lines represents acceptable

 

 

 

 

 

 

 

 

 

 

values for HT and VT

For vent configurations requiring more than one 90° elbow, the following formulas apply:

 

 

Formula 1: HT

< 4.2 VT

 

 

 

 

 

Formula 2: HT

+ VT < 24.75 feet

 

90°

 

H1

H2

 

 

 

 

 

 

 

 

 

 

Example 2:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1

= VT = 6 FT

 

 

FIGURE 3.8b

 

 

90°

 

H1

= 3 FT

 

 

 

 

V1

 

 

 

 

 

 

 

 

 

 

H2

= 5 FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HR

= H1

+ H2

= 3 + 5 = 8 FT

 

 

 

 

 

HO

= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7 FT

 

 

 

 

HT

= HR

+ HO

= 8 + 2.7 = 10.7 FT

 

 

 

 

 

HT

+ VT

= 10.7 + 6 = 16.7 FT

 

 

 

 

 

Formula 1:

 

H

< 4.2 V

 

 

 

 

 

Formula 2:

 

T

4.2 VTT = 4.2 x 6 = 25.2 FT

 

 

 

 

 

HT

+ VT < 24.75 FT

 

 

 

 

90°

 

 

 

 

 

 

16.7 < 24.75

 

 

 

90°

Since both formulas are met, this vent configuration is acceptable.

90°

H

H4

Example 3:

 

 

 

 

 

1

V2

 

 

 

 

 

 

H2

 

 

 

 

 

 

H3

V1

= 4 FT

 

 

 

 

 

 

 

V2

= 1.5 FT

= 4 + 1.5 = 5.5 FT

FIGURE 3.8c

V1

90°

 

V

T

= V + V

2

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

H1

= 2 FT

 

 

 

 

 

 

 

 

 

H2

= 1 FT

 

 

 

 

 

 

 

 

 

H3

= 1 FT

 

 

 

 

 

 

 

 

 

H4

= 1.5 FT

+ H3 + H4 = 2 + 1 + 1 + 1.5 = 5.5 FT

 

 

 

 

HR

= H1

+ H2

 

 

 

 

HO

= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT

 

 

 

 

HT

= HR

+ HO

= 5.5 + 8.1 = 13.6 FT

 

 

 

 

 

HT

+ VT

= 13.6 + 5.5 = 19.1 FT

 

 

 

 

 

Formula 1:

 

HT

< 4.2 VT

 

 

 

 

 

 

 

 

 

 

 

 

4.2 VT = 4.2 x 5.5 = 23.1 FT

 

 

 

 

 

 

 

 

 

 

13.6 < 23.1

 

 

 

 

 

Formula 2:

 

HT

+ VT < 24.75 FT

 

 

 

 

 

 

 

 

 

 

 

19.1 < 24.75

 

 

 

 

 

Since both formulas are met, this vent configuration is acceptable.

16.1_2

W415-0788 / A / 09.22.09

Page 17
Image 17
Napoleon Fireplaces GDS60N manual 3.8TOP EXIT HORIZONTAL TERMINATION, Ht Vt