8.Next construct the hearth extension out of non-combustible inorganic building materials as follows:

a)The hearth extension must extend 17” in front of the rough framed opening on the ZC20.

b)The hearth extension width must be at least 37 15/16”.

c)The hearth extension must be made of brick 2” thick, a listed “Hearth Extension” or “Floor Protector”, or

a hearth extension made of non-combustible inorganic material with a K* factor of: K = 2.5 BTU ((HR) (ft2) (oF/in.))

ALTERNATE FLOOR PROTECTORS MATERIALS

With the floor protector or hearth extension material specified as one layer of 2” thick brick with a K* factor of 5.0, you may use alternate materials as long as the K* factor (s) is calculated as follows:

Formula: Required thickness = (K of alternate material/K of millboard) X (thickness of millboard)

Example: An alternate inorganic non-combustible millboard with a K of .9375 would require a thickness as follows:

Required thickness = .9375.0o x 2 inch = 3/8 inch

K Factors of Alternate Materials:

Material

K

Required Thickness

Ceroform 126

.21

1/8”

Limestone

8.0

3.2”

Concrete

8.0

3.2”

Sandstone

13.0

5.2”

Marble

18.0

7.2”

Hearth extension or floor protector thickness above four (4) inches is generally not acceptable due to cost, floor load capacity, and look. The alternate we recommend is using Ceroform No. 126 millboard 1/8” thick minimum and putting any type decorative brick or stone (any thickness) on top of it.

*The K* factor represents the thermal conductivity of a material and is the time rate of heat flow through a homogeneous material under steady-state conditions, through unit area, per unit temperature gradient in the

direction perpendicular to a surface.

9.The next step is the electrical installation. NOTE: An electrician must wire the ZC20 into the home wiring system using No. 15 AWG (with ground wiring) as minimum in accordance with local wiring codes.

ALTERNATE FLOOR PROTECTORS MATERIALS CAUTION: Stove is plugged into cabinet receptacle.

A.Remove brass trim.

B.Remove top panel and right side panel.

C.Now an electrician must do the wiring.

.

Page 53
Image 53
New Buck Corporation 20 Room Heater manual Alternate Floor Protectors Materials, K Factors of Alternate Materials

FAQ

What materials are required for the hearth extension?

The hearth extension must be made of brick 2 thick, a listed Hearth Extension or Floor Protector, or a hearth extension made of non-combustible inorganic material with a K* factor of 2.5 BTU HR ft2 oF/in.

What is the K factor and why is it important?

The K factor represents the thermal conductivity of a material and is crucial for determining the thickness of alternate floor protector materials.

What wiring specifications should be followed for the ZC20?

An electrician must wire the ZC20 into the home wiring system using No.15 AWG with ground wiring as minimum in accordance with local wiring codes.