New Buck Corporation 20 Room Heater Residential Installations Parts Requirements, Description

Models: 20 Room Heater

1 62
Download 62 pages 31.99 Kb
Page 48
Image 48
RESIDENTIAL INSTALLATIONS

SECTION I

RESIDENTIAL INSTALLATIONS

PARTS REQUIREMENTS

Listed NEW BUCK CORP.

 

 

Model

 

Part Description/Part #

ZC20

Zero clearance cabinet assembly with Model 20

 

fireplace installed

UL Listed and factory approved Chimney Systems

 

 

Description

Simpson Dura Vent

-

6” 2100o HT Type “DP” Chimney

Security

-

6” “ASHT” High Temp Chimney

Selkirk Metal Bestos

-

6” Model SSII Type HT Chimney

Metal Fab

-

6” 2100o HT Chimney

CAUTION: Read through all of these instructions carefully. Follow approved Chimney Manufacturer’s Installation exactly. Failure to install the Cabinet Fireplace, Stove and Chimney as described in the instructions will void the manufacturer’s warranty and may have an effect on your Homeowner’s Insurance. A major cause of chimney related fires is failure to maintain required clearances (air spaces) to combustible materials. It is of utmost importance that these parts be installed only in accordance with these instructions.

The Zero-Clearance cabinet and the Model 20 (hereafter referred to as the ZC20) is designed for installation in a family dwelling, where minimum clearance is desired.

INSTALLATION PRECAUTIONS

The following precautions are mandatory for a safe installation:

A.Compliance with local building codes and regulations is mandatory.

B.Be careful not to damage unit in handling and unpacking component parts and accessories.

C.A UL Listed and Approved Chimney System is to be used and vented to the outside of the building. See chimney list above.

D.The chimney must extend a minimum of 3’ above the highest point where it penetrates the roof (3’ above a flat roof or up to 2 1/2 pitch roof), and the chimney must extend a minimum of 2’ higher than any portion of the building within 10’ of the chimney. The minimum height is 12’. A 2” clearance must be maintained between the chimney and any combustible materials at all points.

E.A rain cap must be used to terminate the chimney to prevent down-draft.

Page 48
Image 48
New Buck Corporation 20 Room Heater Residential Installations Parts Requirements, Installation Precautions, Description

FAQ

What are the mandatory precautions for a safe installation?

The following precautions are mandatory: compliance with local building codes, careful handling of unit during unpacking, use of a UL Listed and Approved Chimney System, and maintaining proper clearances between the chimney and combustible materials.

What is the minimum height requirement for the chimney?

The chimney must extend a minimum of 3 feet above the highest point where it penetrates the roof and 2 feet higher than any portion of the building within 10 feet of the chimney. The minimum height is 12 feet.

Why is it important to follow approved Chimney Manufacturers Installation exactly?

Failure to install the Cabinet Fireplace, Stove, and Chimney as described in the instructions will void the manufacturers warranty and may have an effect on your Homeowners Insurance.