CHASE ENCLOSURE AND CORNER LOCATION FRAMING

Optional

Fire Code Sheet Rock

And Metal Fire Stop

2 In.

Min.

Manual backgroundManual background TOPPER

STORM COLLAR

Manual backgroundManual background ROOF FLASHING

TRIPLE WALL PIPE

CAUTION: Refer to chim- ney manufactures instruc- tions for assembly and disas- sembly of chimney parts. Be sure to follow chimney instructions for proper clear- ances to combustibles and proper air spacing required.

Ceiling

NOTE: Follow building and fire codes for each indi- vidual state.

15FT.

MAX.

NBC

RADIATION

SHIELD

Chase

Enclosure

Manual background 2 “X 4” STUDDING

Manual background USE FIRE CODE SHEET ROCK

NBC METAL FIRE STOP RADIA-

TION SHIELD

2”X 4” STUDDING

A SINGLE HEADER MUST BE

Manual background INSTALLED ABOVE CABINET

34 5/8”

THESE MEASUREMENTS

ARE CRITICAL

37 15/16”Manual background

17”

WARNING: Install the hearth protec- tor only as specified. The hearth exten- sion must extend a minimum of 17” in front of the fireplace opening and must be 37 15/16” wide minimum.

FIGURE 10

CHASE ENCLOSURE AND CORNER LOCATION FRAMING

7.Next construct the hearth extension out of non-combustible inorganic building materials as follows:

a)The hearth extension must extend 17” in front of the rough framed opening on the ZC20.

b)The hearth extension width must be at least 37 15/16”.

c)The hearth extension must be made of brick 2” thick, a listed “Hearth Extension” or “Floor Protector”, or a hearth extension made of non-combustible inorganic material with a K* factor of:

K = 2.5 BTU ((HR) (ft2) (oF/in.))

ALTERNATE FLOOR PROTECTORS MATERIALS

With the floor protector or hearth extension material specified as one layer of 2” thick brick with a K* factor of 5.0, you may use alternate materials as long as the K* factor (s) is calculated as follows:

Formula: Required thickness = (K of alternate material/K of millboard) X (thickness of millboard)

Example: An alternate inorganic non-combustible millboard with a K of .9375 would require a thickness as follows:

Required thickness = .9375.0o x 2 inch = 3/8 inch

Page 58
Image 58
New Buck Corporation 20 Room Heater Chase Enclosure And Corner Location Framing, Alternate Floor Protectors Materials

FAQ

What materials should be used for the hearth extension?

The hearth extension must be made of non-combustible inorganic material with a K factor of 2.5 BTU HR ft2 oF/in.

What are the measurements for the hearth extension?

The hearth extension must extend a minimum of 17 in front of the fireplace opening and must be 37 15/16 wide minimum.

What are the alternate floor protector materials that can be used?

Alternate materials can be used as long as the K factor is calculated using the formula provided in the manual.