9.3.Room Temperature Control (Compressor Control)
Operating frequency of a compressor is decided according to temperature differences between remote controller setting and room temperatures. By adding a relative method, based on current frequency, which gives frequency changes, a room temperature is adjusted.
9.3.1.Cooling Operation
9.3.1.1.Thermostat Control
••
••
••When Room Temperature is below
••The maximum power is applied only for the first 30 minutes of the operation, after that, rated power is applied. If the POWERFUL Switch is pressed during operation, the maximum power will be applied for 30 minutes.
Cooling power | ||
Maximum power | 3.0kW | 4.0kW |
Rated power | 2.6kW | 3.5kW |
Minimum power | 0.6kW | 0.6kW |
9.3.2.Dry Operation
9.3.2.1.Thermostat Control
••The unit can be operated in the Scrolling Dry Operation by selecting Cooling DRY mode with the DRY button on the remote controller.
••
••When Room Temperature exceeds
••The fan speed setting is selectable. → Five stages manually and one stage automatically (QUIET). (Same as Cooling mode.)
9.3.3.Heating Operation
9.3.3.1.Thermostat Control
••
••
••When Room Temperature exceeds
••When operation in rated power continues for 3 minutes or more, it turns to the maximum power.
Cooling power | ||
Maximum power | 6.5kW | 7.7kW |
Rated power | 3.6kW | 4.8kW |
Minimum power | 0.6kW | 0.6kW |
22