1.Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the
••Be sure to connect the end of the charging hose with the push pin to the service port.
2.Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3.Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves form 0 cmHg (0 MPa) to - 76cm Hg
4.Close the Low side valve of the charging set the turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately 5 minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE INORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5.Disconnect the charging hose from vacuum pump and from the service port of the
6.Tighten the service port caps of the
7.Remove the valve caps of both of the
8.Mount valve caps onto the
••Be sure to check for gas leakage.
Caution
••If gauge needle does not move from 0 cmHg (0 MPa) to
••If the leak stops when the piping connections are tightened further, continue working form step 3.
••If the leak does not stop when the connections are retightened, repair the location of leak.
••Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite.
1.Remove the control board cover from the unit by loosening the screw.
2.Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 1.5 mm2 flexible cord, type designation 245 IEC 57
3.Secure the cable onto the control board with the holder (clamper).
4.Attach the control board cover back to the original position with the screw.
1.Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2.If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using
FOR 2 SETS IN ONE ROOM
A switching mechanism to prevent errors occurring in the operation of one of the air conditioners caused by operating the buttons on the remote controller for the other air conditioner is provided. This mechanism was set to “A” at the factory.
Set the other air conditioner and its remote controller to “B”.
••Set the remote controller to “B”.
Open the remote controller’s battery cover, and cut the jumper using a pair of pliers.
••Set the air conditioner to “B”.
1.Hold down the air conditioner’s emergency operation button for at least 11 seconds, and release it after three beeps are heard.
(Note: One beep is heard after the button has been held down for 5 seconds, and two beeps are heard after 8 seconds.)
53