9.15.8.
In Cooling operation
1.When indoor heat exchanger temperature exceeds 45°C in 4 minutes after compressor starts, compressor will be stopped.
2.If the above excess occurs 4 times per 30 minutes, timer lamp is to be blinking. (“F11” is to be confirmed.)
In Heating operation
1.When indoor heat exchanger temperature is below 0°C in 4 minutes after compressor starts, compressor will be stopped.
2.If the above excess occurs 4 times per 30 minutes, timer lamp is to be blinking. (“F11” is to be confirmed.)
9.15.9.Limit of Cooling power
1.When temperature of indoor heat exchanger is below 5°C, operating frequency will be decreased.
2.When temperature of indoor heat exchanger exceeds 7°C, operating frequency will be increased. (But, up to programmed frequency.)
3.When temperature of indoor heat exchanger is below 0°C continuously for 6 minutes, compressor will be stopped.
4.Timer lamp is not blinking. (“F99” is memorized, then.)
Limit of Indoor fan speed
••When temperature of indoor heat exchanger is below 6°C (2°C at Dry) continuously for 6 minutes, indoor fan speed will be increased by 50 rpm.
9.15.10. Outdoor Air Temperature ControlIn Cooling and Dry operations
1.When outdoor air temperature is below 25°C, the maximum power will be limited up to about
2.When outdoor air temperature is below 18°C, the maximum power will be limited up to about
3.When outdoor air temperature is below 11°C, the maximum power will be limited up to about
1.When indoor air temperature is 35°C or more, the maximum power will be limited up to the rated power.
2.When fan speed is set at "Lo" and intake air temperature is below 21°C, the maximum power will be limited up to the rated power.
38