CS-HE9DKE CU-HE9DKE / CS-HE12DKE CU-HE12DKE

13.2.1.2.

Error Code Table

 

 

 

 

 

 

 

 

 

 

Diagnosis

Abnormality / Protection control

Abnormality

Emergency

 

Primary location to verify

display

 

Judgement

operation

 

 

 

 

 

 

 

 

H11

Indoor / outdoor abnormal

> 1 min after starting

Indoor fan operation

••

Internal / external cable

 

communication

operation

only

 

connections

 

 

 

 

•• Indoor / Outdoor PCB

H14

Indoor intake air temperature sensor

••

Intake air temperature sensor

 

abnormality

 

 

 

(defective or disconnected)

H15

Outdoor compressor temperature sensor

Continue for 5 sec.

••

Compressor temperature sensor

 

abnormality

 

 

 

(defective or disconnected)

H16

Outdoor Current Transformer open

••

Outdoor PCB

 

circuit

 

 

•• IPM (Power transistor) module

 

 

 

 

H19

Indoor fan motor mechanism lock

••

Indoor PCB

 

 

 

 

••

Fan motor

H23

Indoor heat exchanger temperature

Continue for 5 sec.

O

••

Heat exchanger temperature

 

sensor abnormality

 

(Cooling only)

 

sensor (defective or disconnected)

H26

Ionizer abnormality

••

Indoor PCB

 

 

 

 

••

Ionizer

H27

Outdoor air temperature sensor

Continue for 5 sec.

O

••

Outdoor temperature sensor

 

abnormality

 

 

 

(defective or disconnected)

H28

Outdoor heat exchanger temperature

Continue for 5 sec.

O

••

Outdoor heat exchanger

 

sensor abnormality

 

 

 

temperature sensor (defective or

 

 

 

 

 

disconnected)

H33

Indoor/Outdoor wrong connection

••

Indoor/Outdoor supply voltage

H97

Outdoor Fan Motor lock abnormality

••

Outdoor PCB

 

 

 

 

••

Outdoor Fan Motor

H98

Indoor high pressure protection

••

Air filter dirty

 

 

 

 

•• Air circulation short circuit

H99

Indoor heat exchanger anti-freezing

••

Insufficient refrigerant

 

protection

 

 

••

Air filter dirty

 

 

 

 

F11

Cooling / Heating cycle changeover

4 times occurrence

••

4-way valve

 

abnormality

within 30 minutes

 

••

V-coil

 

 

 

 

F91

Refrigeration cycle abnormality

2 times occurrence

••

No refrigerant

 

 

within 20 minutes

 

 

(3-way valve is closed)

 

 

 

 

 

F93

Outdoor compressor abnormal revolution

4 times occurrence

••

Outdoor compressor

 

 

within 20 minutes

 

 

 

F95

Cool high pressure protection

4 times occurrence

••

Outdoor refrigerant circuit

 

 

within 20 minutes

 

 

 

F96

IPM (power transistor) overheating

••

Excess refrigerant

 

protection

 

 

••

Improper heat radiation

 

 

 

 

 

 

 

 

••

IPM (Power transistor)

F97

Outdoor compressor overheating

4 times occurrence

••

Insufficient refrigerant

 

protection

within 10 minutes

 

••

Compressor

 

 

 

 

F98

Total running current protection

3 times occurrence

••

Excess refrigerant

 

 

within 20 minutes

 

••

Improper heat radiation

 

 

 

 

F99

Outdoor Direct Current (DC) peak

7 times occurrence

••

Outdoor PCB

 

detection

continuously

 

••

IPM (Power transistor)

 

 

 

 

 

 

 

 

••

Compressor

Note:

“O” - Frequency measured and fan speed fixed.

The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the “RESET” button at remote controller.

Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Codes Table) by using remote controller or Auto Switch at indoor unit. However, the remote controller signal receiving sound is changed from one “beep” to four “beep” sounds.

71