below the top of the chase top. Minimum overlap of

R

7100FP EPA Woodburning Fireplace

For installations utilizing a Round Telescoping Termination

Cap, the uppermost chimney section must be below the

top of the chase top, but not more than 14-1/2 in. (368 mm)

below the top of the chase top. Minimum overlap of

Flashing

chimney and termination cap must be 1-1/2 in. (38 mm).

Collar

2 in.

See Figure 30.1.

 

 

 

Storm Collar

Flashing Collar

2 in. (51 mm) min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14-1/2 in. (368mm) max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of Pipe

 

 

 

1-1/2 in. (38 mm) min.

 

 

 

 

 

 

overlap

Figure 30.1 Installing a TR342 Round Telescoping Termination Cap

NOTE: TR342/TR344: For less air restriction to flue gases, use top vent kit listed in Section 12.

For installations utilizing an ST375 Square Termination Cap the last chimney section must not be more than 4-1/2 in. (114 mm) below the chase top. See Figure 30.2.

(51 mm) min.

 

 

 

 

 

 

 

 

3 in.

1-1/2 in.

 

 

(76 mm)

(38 mm)

Top of Pipe

max.

min.

 

overlap

 

 

 

Figure 30.3 Installing a TS345/TS345P Square Termination Cap

For chase installations you can use a Round Termination Cap, a Round Telescoping Termination Cap, or a Square Termination Cap.

Install termination caps following instructions provided with them.

 

 

 

 

 

 

Flashing Collar

Cap Standoff

 

 

 

 

2 in. (51 mm) min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-1/2 in.

1-1/2 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(38 mm) min.

 

 

 

 

 

(114 mm)

overlap

Top of Pipe

 

 

 

 

 

 

max.

Figure 30.2 Installing an ST375 Square Termination Cap

For installations utilizing a TS345/TS345P Square Termination Cap, the uppermost chimney section must not be more than 3 in. (76 mm) below the chase top. See Figure 30.3.