R
7100FP EPA Woodburning Fireplace
• For installations utilizing a Round Telescoping Termination |
Cap, the uppermost chimney section must be below the |
top of the chase top, but not more than |
below the top of the chase top. Minimum overlap of |
Flashing
chimney and termination cap must be |
Collar
2 in.
See Figure 30.1. |
|
|
| Storm Collar | |||
Flashing Collar | 2 in. (51 mm) min. | |||||
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
| ||||
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
Top of Pipe |
|
|
| |||
|
|
| ||||
|
|
| overlap |
Figure 30.1 Installing a TR342 Round Telescoping Termination Cap
NOTE: TR342/TR344: For less air restriction to flue gases, use top vent kit listed in Section 12.
•For installations utilizing an ST375 Square Termination Cap the last chimney section must not be more than
(51 mm) min.
|
|
|
|
| |
|
|
| 3 in. | ||
| |||||
| (76 mm) | ||||
(38 mm) | Top of Pipe | ||||
max. | |||||
min. |
| ||||
overlap |
|
|
|
Figure 30.3 Installing a TS345/TS345P Square Termination Cap
•For chase installations you can use a Round Termination Cap, a Round Telescoping Termination Cap, or a Square Termination Cap.
•Install termination caps following instructions provided with them.
|
|
|
|
|
| Flashing Collar | ||||||
Cap Standoff |
|
|
|
| 2 in. (51 mm) min. | |||||||
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
| ||||||
(38 mm) min. |
|
|
|
|
| (114 mm) | ||||||
overlap | Top of Pipe |
|
|
|
|
|
| max. |
Figure 30.2 Installing an ST375 Square Termination Cap
•For installations utilizing a TS345/TS345P Square Termination Cap, the uppermost chimney section must not be more than 3 in. (76 mm) below the chase top. See Figure 30.3.
Page 30 | September 7, 2007 |