7100FP EPA Woodburning Fireplace

Manual backgroundWARNING

Fire Risk

Metal hearth strips MUST be installed. Sparks or embers may ignite flooring.

Manual background1in. (25mm) OVERLAP

Metal strips 2 in. (51mm) under edge of Fireplace and Hearth Extension and 2 in. (51mm) on both side of fireplace opening.

Nail or screw metal strips in place.

Figure 39.1 Positioning the Protective Metal Hearth Strips

The construction of, and materials used for a hearth exten- sion are shown in Figures 39.2 and 39.3. A hearth extension of this construction may be covered with any non-combustible decorative material and may have a maximum thickness as per Figure 38.1 on page 38. Seal gaps between the hearth exten- sion and the front of the fireplace with a bead of non-combus- tible sealant.

Manual backgroundWARNING

Fire Risk

Hearth extensions must be installed exactly as specified.

High temperatures or hot embers may ignite concealed combustibles.

Manual background 8 in. (203mm) from each side of fuel loading door

BA

Model # 7100FP

A

B

 

in.

41

20

 

mm

1041

508

Figure 39.2 Hearth Extension Dimensions

1.Fireplace and Hearth Extension are flush on the floor:

2.Fireplace is installed flush on the floor and Hearth Extension is raised to the bottom of the fascia:

Non-combustible flooring 20 in. (508mm) in front of and 8 in. (203mm) to either side of the fuel opening with a minimum thickness of 1 in. (25mm) and (“k” value = 0.49). See Figure 39.2 and 39.3 and Figures 40.1 and 40.2 on page 40.

Raised hearth must be constructed of non-combustible materi- als such as cement block or equivalent material. Non-com- bustible flooring on the raised hearth must be 20 in. (508 mm) in front of and 8 in. (203 mm) to either side of the fuel opening with a minimum thickness of 1 in. (25 mm) and (“k” value = 0.49). See Figure 40.3 on page 40.

NONCOMBUSTIBLE

GAP (SEAL WITH NONCOMBUSTIBLE SEALANT)

DECORATIVE MATERIAL

 

 

 

UP TO BOTTOM OF FASCIA

6 in. (152mm)

1 in. (51mm)

HEARTH METAL STRIPS

 

(2) HX4 MICORE FACTORY

 

BUILT HEARTH EXTENSION

 

 

(Each HX4 = 1/2 in. (13mm) thick)

 

 

Figure 39.3 Side View of Factory Built Hearth Extension

September 7, 2007

433-1390D

Page 39

Page 39
Image 39
Quadra-Fire 7100FP-NL-B, 7100FP-BK-B, 7100FP-GD-B warranty 7100FP EPA Woodburning Fireplace, Fire Risk