7100FP EPA Woodburning Fireplace
WARNING
Fire Risk
•Metal hearth strips MUST be installed. Sparks or embers may ignite flooring.
1in. (25mm) OVERLAP
Metal strips 2 in. (51mm) under edge of Fireplace and Hearth Extension and 2 in. (51mm) on both side of fireplace opening.
Nail or screw metal strips in place.
Figure 39.1 Positioning the Protective Metal Hearth Strips
The construction of, and materials used for a hearth exten- sion are shown in Figures 39.2 and 39.3. A hearth extension of this construction may be covered with any
WARNING
Fire Risk
•Hearth extensions must be installed exactly as specified.
High temperatures or hot embers may ignite concealed combustibles.
8 in. (203mm) from each side of fuel loading door
BA
Model # 7100FP | A | B | |
| in. | 41 | 20 |
| mm | 1041 | 508 |
Figure 39.2 Hearth Extension Dimensions
1.Fireplace and Hearth Extension are flush on the floor:
2.Fireplace is installed flush on the floor and Hearth Extension is raised to the bottom of the fascia:
Raised hearth must be constructed of
NONCOMBUSTIBLE | GAP (SEAL WITH NONCOMBUSTIBLE SEALANT) | |
DECORATIVE MATERIAL |
|
|
| UP TO BOTTOM OF FASCIA | 6 in. (152mm) |
1 in. (51mm) | HEARTH METAL STRIPS |
|
(2) HX4 MICORE FACTORY |
| |
BUILT HEARTH EXTENSION |
|
|
(Each HX4 = 1/2 in. (13mm) thick) |
|
|
Figure 39.3 Side View of Factory Built Hearth Extension