7100FP EPA Woodburning Fireplace
6 Complete the Enclosure
A. Chimney Termination (2-10-03 Rule)
Chimney Termination Requirements (See Figures 26.1 and 26.2)
•Must have a cap approved and listed for this fireplace system
•Must not be located where it will become plugged by snow or other material
•Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft (3.05 m)
•Must be located away from trees or other structures
Slanted Roofs
Chimney must extend 3 ft (914 mm) above the roof
Chimney must extend 2 ft (610 mm) above any portion of the roof
within 10 ft (3048 mm) of the chimney
Flat Roofs
Chimney must extend 3 ft (914 mm) above the roof
Chimney must extend 2 ft (610 mm) above any portion of the roof
within 10 ft (3048 mm) of the chimney
Figure 26.1 Termination Requirements
Gas, Wood or Fuel
Oil Termination
|
| 8 ft |
| A | (2.44 m) |
18 in. | (min. for | |
| 20 in. | |
(457 mm) |
| (508 mm) |
B |
| (min. for direct vent) |
| to | |
|
| Perpendicular |
|
| Wall |
Gas |
|
|
Termination |
|
|
Termination Caps Staggered Height
A | Gas Termination | Wood or Fuel Oil Termination |
B | 6 in. (152 mm) min. | 20 in. (508 mm) min. |
Figure 26.2 Multiple Chimneys
Page 26 | September 7, 2007 |