7100FP EPA Woodburning Fireplace
D. Heat Zone Kit
This kit is tested and safe when installed in accordance with this installation manual. It is your responsibility to read all instructions before starting installation and to follow these instructions carefully during installations.
Installation of this kit MUST by performed by a qualified ser- vice technician.
The
Plan the location of the fireplace and warm air duct run(s).
CAUTION
ALL wiring should be done by a qualified electrician and shall be in compliance with local codes and with the National Electric Code NFPA/NEC No.
DUCT RUN REQUIREMENTS
MAXIMUM Duct Run = 40 ft. (12m) MINIMUM Duct Run = 36 in. (914mm)
DUCTING MATERIAL
6 in. (152mm)
DO NOT DUCT into existing furnace plenum
MINIMUM CLEARANCE TO COMBUSTIBLES
1 in. (25mm) from the
1/2 in. (13mm) from top & bottom of outlet box 0 in. (0mm) from the sides of outlet box
12 in. (305mm) from wall register to ceiling* *(See Figure 33.1).
Possible Air Duct Runs / Locations
12 in. (305mm) minimum clearance from register to ceiling
Ceiling Register
Wall Register
Floor Register
Ceiling Register
Two Duct Kits
Figure 33.1 Minimum Clearances to Combustibles
September 7, 2007 | Page 33 |