Quadra-Fire 7100FP-GD-B Finishing, 7100FP EPA Woodburning Fireplace, A. Hearth Extension, Table

Models: 7100FP-BK-B 7100FP-GD-B 7100FP-NL-B

1 68
Download 68 pages 44.2 Kb
Page 38
Image 38
8 Finishing

7100FP EPA Woodburning Fireplace

8 Finishing

A. Hearth Extension

A hearth extension must be installed with all fireplaces to protect the combustible floor in front of the fireplace from both radiant heat and sparks. See Figures 38.1 below, and Figures 39.1 and 39.2 on page 39.

 

High temperature

 

 

 

 

(300°F min.) continuous,

 

 

HX3 or HX4

non-combustible sealant

Fireplace

 

non-combustible material

Protective

insulation

Hearth Ext

Tile, stone or other

 

 

or equivalent

 

 

 

 

 

 

(see Table below)

 

 

 

Metal Hearth

 

 

 

 

Strip

 

 

2 in. (51 mm)

 

 

Floor constructed of wood or

required

 

 

other combustible material

 

 

 

Figure 38.1 Hearth Extension Construction

A. Hearth ExtensionWARNING

Fire Risk

Maintain clearances.

Use only non-combustible material below standoffs, material such as cement board is acceptable.

Framing or finishing material used on the front of, or in front of, the appliance closer than the minimums listed, must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.).

B.Calculating Alternate Floor Protection Material

Thermal Conductivity: k value

The k value indicates the amount of heat (in BTU’s) that will flow in 1 hour through 1 square foot of a uniform material 1 inch thick for each degree (F) of temperature difference from one side of the material to the other. The LOWER the k factor means less heat is being conducted through the non-combustible material to the combustible material beneath it. The k value of a mate- rial must be equal or smaller then the required k value to be acceptable.

(BTU) (inch) (foot2 (hour) (oF)

Thermal Resistance: R value

The R value is a measure of a material’s resistance to heat transfer. R value is convenient when more than one material is used since you can add the R values together, whereas you can not do this for k value. The HIGHER the R

R

factor means less heat is being conducted through the non- combustible material to the combustible material beneath it. The R value of a material must be equal or larger then the required R value to be acceptable.

Converting k to R:

Divide 1 by k and multiply the results times the thickness in inch- es of the material.

R = 1/k x inches of thickness

Converting R to k:

Divide the inches of thickness by R. k = inches of thickness/R

Calculations:

Example: Floor protection requires k value of 0.84 and 3/4 inch thick.

Alternative material has a k value of 0.6 and is 3/4 inch thick.

Divide 0.6 by .75 = k value of 0.80. This k value is smaller than 0.84 and therefore is acceptable.

Table 38.2

Hearth Extension Insulation Alternatives, R Value = 1.16

 

 

 

Minimum

Material

k per inch

R per inch

thickness

thick

thick

required

Hearth & Home HX3, HX4

0.49

2.18

1 in.

USG Micore 300™

0.49

2.18

1 in.

USG Durock™ Cement Board

1.92

0.52

2-1/4 in.

Cement Mortor

5.0

0.20

5-7/8 in.

Common Brick

5.0

0.20

5-7/8 in.

Ceramic Tile

12.50

0.08

14-5/8 in.

Armstrong™ Privacy

 

 

 

Guard Plus

0.046

2.18

1/2 in.

Marble

14.3-20.0

0.07-0.05

16-5/8 in. - 23-3/8 in.

Page 38

433-1390D

September 7, 2007

Page 38
Image 38
Quadra-Fire 7100FP-GD-B Finishing, 7100FP EPA Woodburning Fireplace, A. Hearth Extension, Table, Fire Risk, Calculations