R

Mt. Vernon Pellet Insert (AE)

Built-In Vertical

3.0 in

(76mm)

3.0 in

(76mm)

7.5 in

(191mm)

Use two 45 degree elbows to clear heat shield and hopper.

Figure 9.1

C. Masonry and Zero Clearance Fireplaces

 

Mantel

Face

 

 

Trim

Wall

 

B

 

 

Side

A

C

 

 

 

E

D

Figure 9.2

 

Location

INCHES

MILLIMETERS

 

 

 

 

A

Insert side to combustible side wall

6

152

 

 

 

 

B

Insert top to max. 2-1/4 inch face trim

0

0

 

 

 

 

C

Insert side to max. 2-1/4 inch face trim

0

0

 

 

 

 

D. Floor Protection

 

Location

INCHES

MILLIMETERS

 

 

 

 

D

Floor protection hearth extension from

6

152

 

door opening

 

 

 

 

 

 

 

E

Floor protection to the side of door

6

152

 

opening

 

 

 

 

 

 

Use a non-combustible fl oor protector, extending beneath appliance and to the front, and sides as indicated.

If employing a hearth extension, any parts or materials used in construction must be non-combustible.

E.Minimum Opening for Masonry and Zero Clearance Fireplaces

H

G

F

I

Figure 9.3

 

Location

Inches

Millimeters

 

 

 

 

F

Rear Width

24

610

 

 

 

 

G

Depth

15

381

 

 

 

 

H

Height

23-7/8

606

 

 

 

 

I

Front Width

34

864

 

 

 

 

F. Mantel Projections

J

K

Figure 9.4

The maximum mantel depth (J) is 12 inches (305mm) with a minimum vertical height (K) of 12 inches (305mm).

However if your mantel has a depth of 10 inches (254mm) then the vertical minimum height is 10 inches (254mm).

November 22, 2011

7036-135G

Page 9

Page 9
Image 9
Quadra-Fire MTVERNINSAE-PMH Mt. Vernon Pellet Insert AE Built-In Vertical, Masonry and Zero Clearance Fireplaces