VENT RESTRICTOR SETTING:

INSTALLATION

VENTING ARRANGEMENTS

ALLOWABLE HORIZONTAL TERMINATIONS

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o two 45o elbows equal one 90o elbow).

Note: Must use optional rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems.

VENT RESTRICTOR SETTING:

Vent restrictor factory set, no adjustment required unless otherwise indicated.

Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 1 to Set 2 or Set 4 if required.

Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.

Maintain clearances to combustibles as listed in "Clearances" section

Horizontal vent must be supported every 3 feet.

Firestops are required at each floor level and whenever passing through a wall.

A wall thimble is mandatory for all horizontal terminations due to high temperatures.

INSTALLATION

Regency® L676-1 Direct Vent Gas Fireplace

19

Page 19
Image 19
Regency L676-1, L676-NG1, L676-LP1 installation manual Installation, Venting Arrangements, Vent Restrictor Setting