DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

16.4 Flue Fan

Rear Panel

Flue Adapter

Hole to Flue Fan screws

Vent Box

Vent Box

 

Flue

Outlet

Adapter

screws

 

Gasket

 

 

Flue Fan

 

 

Disconnect

 

electrical connections

 

at plug in tabs.

Remove screws securing outlet flange to the flue adapter.

 

Mounting

Vent Box

 

 

 

Plate

 

Gasket

 

Mounting Plate

 

to Vent Box

 

 

screws

 

 

Gasket

Mounting Plate

 

Air Plate

to Flue Fan

 

 

 

screws

 

 

Remove screws securing flue fan mounting plate to vent box Remove screws securing mounting plate to fan.

Refit in reverse. Use new gaskets. Ensure sealed joints.

Ensure mounting plate orifice is clear and not obstructed.

 

 

MODEL

75

90

100

115

 

 

Flue Fan

AO Smith

AO Smith

AO Smith

Torin DSF

 

 

146-052

 

 

JFIG07INS

JFIG07INS

JFIG07INS

 

 

 

 

077274

 

 

 

 

 

 

 

 

 

RG P/N

90710001

90710001

90710001

90710450

 

 

Air

mm dia

97.0

103.6

110.5

152.4

 

 

Plate

in dia

3.82

4.08

4.35

6

 

 

RG P/N

11011134

11011133

11011132

11011131

 

IT IS IMPORTANT THAT ONLY THE CORRECT FLUE FAN SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.

Carry out a commission after working on or changing a flue fan. See Page 25, Section 12.

38

Page 44
Image 44
Roberts Gorden DAT75, DAT90, DAT100, DAT115 service manual Remove screws securing outlet flange to the flue adapter