DAT100 DAT115
DualAir
If you smell gas
Quality in Any Language
Page
2005
TABLE OF CONTENTS
Page
TABLE OF FIGURES
Page
Product Approval
SECTION 2 INSTALLER RESPONSIBILITY
SECTION 1 HEATER SAFETY
2.1 Clearances to Combustibles
2.2 Corrosive Chemicals
3.7 Electrical Supply
3.3 Minimum Required Installation Clearances
3.8 Flue
3.9 Coil Condense Drain
80 cm is necessary to service heater
SECTION 4 SPECIFICATIONS 4.1 DAT all models
Front View
Front View Left Version
4.2 General Technical Data Table all models
4.3Technical Data Table - Heater Section all models Appliance Category II 2H/L 3B/P
4.4.2 DAT100 and 115 4 kW motor
5.2 Handling
SECTION 5 HEATER INSTALLATION 5.1 General
5.3 Shelf Mounting and Suspension
Figure 3 Suspension Methods
6.3 Type B22 Appliance
terminal. See Page 12, Figure
See Page 10, Figure 4 through Page 12, Figure
6.3.1 Air Intake Terminal Cover
Figure 6 Alternate
Figure 5 Control Section & Upper Panel
Masterflash
Roof Terminal
Metal Sleeve
25 mm air gap to combustible material Flue
7.2 Open Flued Installation
7.1 Room Sealed Installation
7.2.1 Heaters Installed Within the Heated Space
SECTION 7 AIR SUPPLY
duct resistance and design. Tel +44
Department for recommendations regarding
494425
Figure 10 Ducting
9.1 Connections
SECTION 9 GAS PIPING
10.2 Remote Control
SECTION 10 WIRING AND ELECTRICAL INFORMATION
10.1 Electrical Supply
10.2.1 Remote Frost Thermostat
Relay/Function
Terminal
Operation
Number
10.4 DAT Wiring Diagram Models
See Page 20, Section
SITE WIRING
10.5 DAT Wiring Diagram Models
Site wiring connections shown
SECTION 10 WIRING AND ELECTRICAL INFORMATION
10.6 DAT Site Connections at Main Circuit Board
Cooling Coils/Condensers
SECTION 11 COMMISSIONING Gas Fired Heater
11.1 Pre Commission Checks
11.1.1 Louvers
Figure 13 Modureg Gas Valve
Figure 12 Automatic Burner Control Box Sequence
Required Incoming Signals
Signals Output By Control
11.5 Combustion Testing all models
two adjustments. See Page 22, Figure
11.4.2 Commissioning the Gas Valves
See Page 22, Figure
11.6 Turning Off the DualAir Unit
Pressure Switch
11.7 External Controls
11.8 Complete the Commissioning
See Page 25, Section
See Page 26, Section
12.2 Heater Operation
12.2.1 Warning Lights
12.6 Simple Fault Finding all models
12.3.3 Burner Lockout Reset Button
12.6.1 Simple Fault Finding burner faults
12.4 Cooling Section Operation
13.3 Fan/Motor Assembly Maintenance
13.2 Burner Maintenance
13.4 Heat Exchanger Maintenance
SECTION 13 SERVICING 13.1 Servicing Instructions
Replace faulty gas valves with genuine
13.5 Gas Control Valve Maintenance all models
ROBERTS GORDON replacement parts 13.6 Flue Fan
Do not repair or disassemble on site
SECTION 14 CONVERSION BETWEEN GASES 14.1 General
14.2 Burner Conversion
14.3 Gas Valves
Start
SECTION 15 TROUBLESHOOTING 15.1 General
values, then reverse the test leads
START
15.3 Troubleshooting for Flame Supervision System
TROUBLESHOOT ENDS
damaged? Is the flame probe
15.5 Troubleshooting for Main Fan
15.4 Troubleshooting for Solenoid Valves
START
START
15.6 Troubleshooting for Fan Contactor
START
TROUBLESHOOT ENDS
16.1.1 Gas Valve Replacement - all models
SECTION 16 REMOVAL AND REPLACEMENT PARTS
Burner Components
See Page 5, Section
16.2.1 Burner Injectors
16.2 Burner Compartment
Ensure gas tight fitting of injectors
Ensure correct alignment with burners
16.3 Ignition Electrode and Flame Probe
16.4 Flue Fan
See Page 21, Section
16.5 Heater Pressure Switch
Coil Pressure Switch
16.6.2 Pressure Switches
Filter Pressure Switch
Figure 18 Cooling Coil Safety Devices
16.7 Ignition Control
16.7.1 S4563C Models 75 to
16.8 Fan Motor Removal
16.8.1 Fan Removal and Replacement
Figure 19 Combination Fan/Limit Thermostat
Fire Hazard
Heat exchanger damage may result
Page
Page
80 cm is necessary to service heater
Installation Clearances
Fire Hazard
close to heater