OPERATING INSTRUCTIONS

Attach this information to the wall near the ROBERTS GORDON® heater

®

Read the installation, Commissioning, Operation and Service Manual thoroughly before installation, operation or service.

OPERATING INSTRUCTIONS

WARNING

 

 

 

 

 

1.STOP! Read all safety instructions on this information sheet.

2.Open the manual gas valve in the heater supply line.

3.Turn on electric power to the heater.

4.Set the thermostat to desired setting (above ambient temperature).

The automatic starting sequence begins.

NOTE: Following long shutdown periods, the burner control may go to to 'LOCKOUT' during the start sequence. Push the reset button to recommence firing. Contact service department if 'LOCKOUT' continues (see manual for details).

TO TURN OFF THE HEATER

 

 

Fire Hazard

1.

Turn the thermostat/time switch to 'OFF'. The burner will turn 'OFF'

 

immediately, but fans will continue to cool heat exchanger until the fan

Some objects can catch fire or explode when placed

thermostat switches off.

 

 

close to heater.

IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,

 

FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER

Keep all flammable objects, liquids and vapors the

 

 

required clearances to combustibles away from heater.

1.

Set the thermostat to off or the lowest setting.

 

2.

Turn off electric power to the heater.

Failure to follow these instructions can result in death,

3. Turn off the manual gas valve in the heater supply line.

injury or property damage.

4.

Call your registered installer/contractor qualified in the installation

 

 

and service of gas-fired heating equipment.

 

Installation Clearances

Roof Terminal

 

 

Alternative

Air

Flue

Wall

Intake

Terminal

 

15 cm

 

 

 

 

Air Flow

 

 

Condense Drain

 

 

Install to

 

 

suitable drain

 

 

60 cm

3 m

 

 

 

Insulated

 

2.5 - 3.5 m*

Refrigerant pipes

 

to cooling coil

Customers

 

by Customer

 

Suitable

 

 

Condenser

 

 

Unit

Clearances to Combustibles

 

15 cm

50 cm

50 cm**

 

30 cm

**80 cm is necessary to service heater.

Roberts-Gordon, LLC

Telephone: 716.852.4400

Roberts-Gordon Europe Limited

Service Telephone: +44(0) 1902 498733

1250 William Street

Fax: 716.852.0854

Oxford Street

Service Fax: +44(0) 1902 401464

P.O. Box 44

Toll Free: 800.828.7450

Bilston, West Midlands WV14 7EG UK

E-mail: uksales@rg-inc.com

Buffalo, NY 14240-0044 USA

 

Telephone: +44(0) 1902 494425

E-mail: export@rg-inc.com

 

Fax: +44(0) 1902 403200

 

 

 

 

Installation Code and Annual Inspections: All installations of ROBERTS GORDON® products must be performed by a contractor qualified in the installation and service of gas-fired heating equipment and conform to all requirements of all applicable governmental authorities pertaining to the installation and operation of the equipment.

For optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® products and perform service where necessary, using only ROBERTS GORDON® replacement parts.

©2005 ROBERTS GORDON® All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon.

www.rg-inc.com