DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

WARNING

Fire Hazard

Some objects will catch fire or explode when placed close to heater.

Keep all flammable objects, liquids and vapours the required distance away from the heater.

Failure to follow these instructions can result in death, injury or property damage.

Figure 2: Installation Clearances and Clearances to Combustibles

Installation Clearances

Roof Terminal

 

 

 

Alternative

Air

Flue

 

Wall

Intake

 

Terminal

 

 

15 cm

 

 

 

 

 

 

Condense

 

 

Air Flow

Drain

 

 

Install to

 

 

 

suitable drain,

 

 

 

See Page 3,

 

 

 

Figure 1.

 

 

60 cm

 

3 m

 

 

 

 

Insulated

 

 

2.5 - 3.5 m*

Refrigerant pipes

 

 

to cooling coil

Customers

 

 

by Customer

 

 

Suitable

 

 

 

Condenser

 

 

 

Unit

 

*Free blowing DualAir® units may be mounted at a higher level if destratification fans and/or turn down nozzles are installed.

Clearances to Combustibles

15 cm

50 cm

50 cm**

30 cm

**80 cm is necessary to service heater.

Free blowing DualAir® units must always be installed at least 1.8 m above the floor. Ducted installations may be floor mounted.

The flue pipe must have clearance from combustibles by 5 cm.

If installed at low levels where individuals can come in contact with hot heat exchanger components, adequate guarding must be provided.

All distances are minimum clearance requirements for service access, air flow and safety.

4

Page 10
Image 10
Roberts Gorden DAT100, DAT75, DAT90, DAT115 service manual Installation Clearances and Clearances to Combustibles