15.3 Troubleshooting for Flame Supervision System

DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

15.3 Troubleshooting for Flame Supervision System

START

Connect a DC ammeter in series with the flame probe.

Is the green light on and at least 1 µA DC fame current?

Yes

Is there a current flowing in the flame probe circuit with no flame present?

No

Does “lockout” occur when there is a flame present?

No

Heater Operating

TROUBLESHOOT ENDS.

No

Use section 15.1 to

 

 

trace the fault.

 

 

 

Is the connecting lead

 

Repair or replace as

Yes

damaged? Is the flame probe

Yes

damaged or touching earthed

necessary.

 

components?

 

 

 

Is inlet burner gas pressure

 

 

Yes

correct? Is live and neutral

Yes

Control box faulty.

polarity correct? Is

Replace with correct type.

 

flame probe circuit correct?

 

 

 

No

 

 

 

Repair or replace as

 

 

 

necessary.

 

 

 

If problems persist, contact

 

 

 

ROBERTS GORDON® at

 

 

No

Tel: +44 (0) 1902 498733

 

 

 

www.combat.co.uk

 

 

 

or www.rg-inc.com

 

 

NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.