15.3 Troubleshooting for Flame Supervision System
START
Connect a DC ammeter in series with the flame probe.
Is the green light on and at least 1 µA DC fame current?
Yes
Is there a current flowing in the flame probe circuit with no flame present?
No
Does “lockout” occur when there is a flame present?
No
Heater Operating
TROUBLESHOOT ENDS.
No  | Use section 15.1 to  | 
  | 
  | 
trace the fault.  | 
  | 
  | |
  | Is the connecting lead  | 
  | Repair or replace as  | 
Yes  | damaged? Is the flame probe  | Yes  | |
damaged or touching earthed  | necessary.  | ||
  | components?  | 
  | 
  | 
  | Is inlet burner gas pressure  | 
  | 
  | 
Yes  | correct? Is live and neutral  | Yes  | Control box faulty.  | 
polarity correct? Is  | Replace with correct type.  | ||
  | flame probe circuit correct?  | 
  | 
  | 
  | No  | 
  | 
  | 
  | Repair or replace as  | 
  | 
  | 
  | necessary.  | 
  | 
  | 
  | If problems persist, contact  | 
  | 
  | 
  | ROBERTS GORDON® at  | 
  | 
  | 
No  | Tel: +44 (0) 1902 498733  | 
  | 
  | 
  | www.combat.co.uk  | 
  | 
  | 
  | or   | 
  | 
  | 
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 
32