4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram

Indoor Unit KHS1872

Outdoor Unit CH1872

KHS2472

CH2472

Indoor unit

Outdoor unit

 

Wide tube

Accumulator

Compressor

Wide tube

service

 

 

 

valve

 

 

 

 

 

High pressure

 

*1

Muffler

switch

 

 

H.P.

 

 

 

 

 

 

 

4-way

 

 

 

valve

 

 

Heat exchanger

 

 

 

Heat exchanger

 

 

 

Capillary

 

 

 

Electric

tube for

 

 

Narrow

split flow

 

 

expansion

 

 

 

tube

 

 

 

valve

 

 

 

service

 

 

Narrow tube

M

 

 

valve

 

 

O.D.

Strainer

 

 

 

1/4"

 

 

 

 

(6.35 mm)

 

 

 

 

*1

O.D.1/2"(12.7 mm)

......... 1872 class

 

 

 

O.D.5/8"(15.88 mm) ......... 2472 class

 

 

Cooling cycle (Defrosting cycle)

Heating cycle

Insulation of Refrigerant Tubing

IMPORTANT

Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 5/16"(8 mm).

Thickness:

Min. 5/16"(8 mm)

Insulation

Thickness:

Min. 5/16"(8 mm)

After a tube has been insulated,

CAUTION never try to bend it into a narrowWide tube curve because it can cause the tube

to break or crack.

Narrow tube