(3) Serial Communication Error Identification Procedure

If the lamps on the main body show the following conditions after the completion of self-diagnostics, a communication error between the indoor unit and outdoor unit might be considered.

In such a case, identify the breakdown section by using the following procedure.

NOTE Refer to "Method of Self-Diagnostics" for the self-diagnostics procedure.

Lamp

Condition

E01

E12

Quiet

(3)

Timer Operation

(2)(1)

: Off

: Blinking

: Illuminated

< Before the Operation >

WARNING

CAUTION

For terminal strip short circuit work or inter-unit wiring removal, turn off the power to avoid an electric shock.

Release the terminal strip short circuit after the completion of self-diagnostics.

Do not perform the short-circuit work between any other terminals except for specified ones on the specified terminal strip. If such work is performed between the incorrect terminals, the unit might be broken.

< Convenient Tool for Short-Circuit Work ( for example ) >

Cable

Alligator Clip

Alligator Clip

 

< Check Items before Troubleshooting Serial Communication Start >

After confirming that the following errors do not exist, start the "Troubleshooting Serial Communication" in "Condition: E01 and E12".

1.

Mis -wiring (inter-unit cable, etc.)

6.

Reactor failure (defective insulation, etc.)

2.

AC power failure

7.

High-Pressure Switch failure

3.

Blown fuse

8.

Overload Relay failure

4.

Power Relay failure

9.

Magnetic Coil failure (defective insulation, short-circuit, etc.)

5.

Outdoor Fan Motor failure (defective insulation, etc.)

10. Compressor failure (defective insulation, etc.)

(3-1) Condition: E01

Troubleshooting Serial Communication

 

 

-

+

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

1

 

2

 

3

4

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

3

 

4

 

5

 

6

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

 

 

 

 

1

2

 

3

 

 

 

 

 

 

 

 

V

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1

 

 

 

 

 

 

 

 

 

 

Fig. 2

Is the voltage of about DC12V

or more given between the terminalsNo

2 and 3 on the outdoor unit terminal strip

(Serial Communication Line) ?

(Fig. 1)

Yes

A

( Continued to the next page A. )

1.Turn OFF the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF.

2.Disconnect the cable from the terminal 3 on the indoor unit

terminal strip. (Fig. 2)

3.Turn ON the power.

B

( Continued to the next page B. )

46

Page 46
Image 46
Sanyo CH2472, CH1872 Serial Communication Error Identification Procedure, Off Blinking Illuminated, Before the Operation