Sanyo CH2472, CH1872 service manual How to connect wiring to the terminal

Models: CH1872 CH2472

1 111
Download 111 pages 55.76 Kb
Page 98
Image 98
How to connect wiring to the terminal

WARNING Loose wiring may cause the terminal to overheat or result

in unit malfunction. A fire hazard may also exist. There- fore, be sure all wiring is tightly connected.

When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate.

How to connect wiring to the terminal

a) For Indoor Unit

9/32"

STRIP (7 mm) (ACTUAL

SIZESIZE)

(1)Cut the wire end with a cutting pliers, then strip the insulation to expose the wire about 9/32" (7 mm). See the label (Fig. 28) near the terminal plate.

(2)Using a screwdriver, loosen the terminal screw on the terminal plate.

(3)Insert the wire and tighten the terminal screw com- pletely using a screwdriver.

b) For Outdoor Unit

For solid core wiring (or F-cable)

(1)Cut the wire end with a cutting pliers, then strip the insulation to expose the solid wire about 15/16" (25 mm). (Fig. 29)

(2)Using a screwdriver, remove the terminal screw(s) on the terminal plate.

(3)Using the pliers, bend the solid wire to form a loop suitable for the terminal screw.

(4)Shape the loop wire properly, place it on the termi- nal plate and fix it securely with the removed termi- nal screw using a screwdriver.

For stranded wiring

(1)Cut the wire end with a cutting pliers, then strip the insulation to expose the stranded wiring about 3/8" (10 mm) and tightly twist the wire ends. (Figs. 30 and 31)

(2)Using a screwdriver, remove the terminal screw(s) on the terminal plate.

(3)Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring connector. (Fig. 30)

(4)Place the ring connector wire, and replace and tighten the removed terminal screw using a screw- driver. (Fig. 32)

Special washer

Wire

Fig. 28

Strip 15/16" (25mm)

Solid wire

Insulation

 

 

Fig. 29

Strip 3/8" (10 mm)

Stranded wire

 

Fig. 30

Twist wire ends

Fig. 31

Screw

Ring connector

Terminal plate

Wire

Fig. 32

Loop

Ring connector

Screw and

special washer

Ring

connector

12

Page 98
Image 98