10. CHECKING ELECTRICAL COMPONENTS

10-1. Measurement of Insulation Resistance

Ground wire

The insulation is in good condition if the resistance exceeds 1M ohm.

10-1-1. Power Supply Cord

Clamp the grounding wire of power cord with the lead clip of the insulation resistance tester and measure the

Clip

Probe

Fig. 1

Insulation tester

resistance by placing a probe on either of the two power wires. (Fig. 1)

Then also measure the resistance between the grounding and other power terminals. (Fig. 1)

Terminal plate

Probe

10-1-2. Indoor Unit

Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate. (Fig. 2)

Note that the ground line terminal should be skipped for the check.

10-1-3. Outdoor Unit

Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate. (Fig. 2)

10-1-4. Measurement of Insulation Resistance for Electrical Parts

Disconnect the lead wires of the desired electric part from terminal plate, capacitor, etc. Similarly disconnect the connector. Then measure the insulation resistance. (Figs. 3 and 4)

NOTE

Refer to Electric Wiring Diagram.

If the probe cannot enter the poles because the hole is too narrow then use a probe with a thinner pin.

Clip

Copper tube or metallic part

Clip

Copper tube or metallic part

Metallic part

Clip

Insulation tester

Fig. 2

Probe

Insulation tester

Fig. 3

From fan motor, compressor and other parts

Probe

Fig. 4

Insulation

tester

52

Page 52
Image 52
Sanyo CH2472, CH1872 service manual Checking Electrical Components, Measurement of Insulation Resistance, Power Supply Cord