Indoor Unit

: KHS2472

 

 

 

 

 

 

 

 

 

Outdoor Unit

: CH2472

 

 

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

< Heating Capacity >

 

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

29,000 BTU/h

 

AIR FLOW RATE:

 

653 CFM

 

 

OUTDOOR

 

 

 

 

 

INDOOR

 

 

 

 

ENT. TEMP. oF (oC)

 

 

 

 

AMBIENT TEMP. oF (oC)

 

 

 

 

 

W.B.

 

 

 

60

65

 

70

75

 

80

 

 

 

 

 

 

 

(15.6)

(18.3)

 

(21.1)

(23.9)

 

(26.7)

 

 

0

(-17.8)

 

TH

 

16,210

16,210

 

16,200

16,180

 

16,150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

(-16.1)

 

TH

 

16,750

16,750

 

16,740

16,720

 

16,690

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

(-13.3)

 

TH

 

18,050

18,050

 

18,040

18,010

 

17,980

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

(-10.6)

 

TH

 

19,390

19,390

 

19,380

19,350

 

19,320

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

(-7.8)

 

TH

 

20,870

20,860

 

20,850

20,820

 

20,780

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23

(-5.0)

 

TH

 

22,420

22,410

 

22,390

22,360

 

22,320

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

(-2.2)

 

TH

 

24,030

24,020

 

24,000

23,960

 

23,910

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33

(0.6)

 

TH

 

25,690

25,680

 

25,650

25,610

 

25,550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38

(3.3)

 

TH

 

27,330

27,320

 

27,280

27,230

 

27,160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43

(6.1)

 

TH

 

29,070

29,040

 

# 29,000

28,940

 

28,860

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48

(8.9)

 

TH

 

30,820

30,790

 

30,740

30,670

 

30,580

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

53

(11.7)

 

TH

 

32,580

32,540

 

32,470

32,390

 

32,300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58

(14.4)

 

TH

 

34,260

34,210

 

34,140

34,050

 

32,390

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

(17.2)

 

TH

 

35,980

35,920

 

35,840

33,980

 

32,250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

(18.3)

 

TH

 

36,640

36,580

 

35,780

33,880

 

32,150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH : Total Heating Capacity (BTU/h)

NOTE

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 70 °F (21.1 °C) D.B.

:Outdoor Ambient Temp. 47 °F (8.3 °C) D.B. / 43 °F (6.1 °C) W.B.

2.Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air Prevention Protection during heating operation into account. For this reason, the value may vary from the actual heating characteristics.

3.Above data represents the value when the operation frequency of a compressor is fixed.