Sanyo CH1872, CH2472 service manual Electrical Data, Electrical Characteristics

Models: CH1872 CH2472

1 111
Download 111 pages 55.76 Kb
Page 31
Image 31

6. ELECTRICAL DATA

6-1. Electrical Characteristics

Indoor Unit

KHS1872

 

 

 

 

Outdoor Unit

CH1872

 

 

 

 

(1) Voltage:230V

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

< 230V >

 

 

 

 

 

Indoor Unit

Outdoor Unit

Complete Unit

 

 

 

 

 

Fan Motor

Fan Motor + Compressor

 

 

 

 

 

 

Performance at

 

 

 

 

230V Single-phase 60Hz

 

Rating conditions

 

Running amp.

A

0.3

6.7

7.0

 

 

 

Power input

W

32

1,468

1,500

Rating conditions:

Indoor air temperature:

80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.

 

 

 

Outdoor air temperature:

95°F (35°C) D.B.

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

Outdoor Unit

Complete Unit

 

 

 

 

 

Fan Motor

Fan Motor + Compressor

 

 

 

 

 

 

Performance at

 

 

 

 

230V Single-phase 60Hz

 

Rating conditions

 

Running amp.

A

0.3

7.1

7.4

 

 

 

Power input

W

34

1,541

1,575

Rating conditions:

Indoor air temperature

70°F (21.1°C) D.B.

 

 

 

 

Outdoor air temperature

47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.

 

(2) Voltage:208V

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

< 208V >

 

 

 

 

 

Indoor Unit

Outdoor Unit

Complete Unit

 

 

 

 

 

Fan Motor

Fan Motor + Compressor

 

 

 

 

 

 

Performance at

 

 

 

 

208V Single-phase 60Hz

 

Rating conditions

 

Running amp.

A

0.3

7.4

7.7

 

 

 

Power input

W

32

1,468

1,500

Rating conditions:

Indoor air temperature:

80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.

 

 

 

Outdoor air temperature:

95°F (35°C) D.B.

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

Outdoor Unit

Complete Unit

 

 

 

 

 

Fan Motor

Fan Motor + Compressor

 

 

 

 

 

 

Performance at

 

 

 

 

208V Single-phase 60Hz

 

Rating conditions

 

Running amp.

A

0.3

7.8

8.1

 

 

 

Power input

W

34

1,541

1,575

Rating conditions:

Indoor air temperature

70°F (21.1°C) D.B.

 

 

 

 

Outdoor air temperature

47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.

 

31