9-3. Checking the Indoor and Outdoor Units

9-3. Checking the Indoor and Outdoor Units

(1) Checking the indoor unit

No.

Control

Check items (unit operation)

1

Use the remote controller to operate the

The rated voltage must be present between inter-unit wirings 1 and 2.

 

unit in "TEST run" mode. To determine

Connect a 5 k ohm resistor between inter-unit wirings 2 and 3. When the

 

whether the mode is currently in

voltage at both ends is measured, approximately 12 to 15V DC must

 

"TEST run" mode, check the 4 indicator

be output and the multimeter pointer must bounce once every 8

 

lamps on the unit. If all 4 are blinking,

seconds.

 

the current mode is "TEST run."

Or instead of measuring the voltage, you can insert an LED jig and

 

 

check that the LED flickers once every 8 seconds.

If there are no problems with the above, then check the outdoor unit.

For the "Test run" procedure, refer to the Appendix B "Installation Instructions".

(2) Checking the outdoor unit

 

No.

Control

Check items (unit operation)

1 Apply the rated voltage between outdoor

The control panel LED (red) must illuminate.

 

unit terminals L and N.

 

2Short-circuit the outdoor unit COM terminal The compressor, fan motor and 4-way valve must all turn on. to the T-RUN terminal.

Manual background If there are no problems with the above, then check the indoor unit.

Using the TEST/T-RUN terminals

 

TEST/T-RUN terminals

 

 

 

 

 

 

 

 

 

 

T-RUN : Test run (compressor and fan motor turn ON).

 

 

 

 

 

 

 

 

 

 

TEST/MV : Compresses time to 1/60th (accelerates

 

 

 

 

 

 

 

 

 

 

operation by 60 times faster than normal).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(TEST)/MV

 

T-RUN

 

COM

45