Indoor Unit

: KHS2472

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

: CH2472

 

 

 

 

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

 

< Cooling Capacity >

 

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

24,200 BTU/h

 

AIR FLOW RATE:

600 CFM

 

INDOOR

 

 

 

 

OUTDOOR

 

 

 

 

 

ENT. TEMP. oF (oC)

 

 

AMBIENT TEMP. oF (oC)

 

 

 

W.B.

 

D.B.

 

65

75

85

 

95

105

115

 

 

 

 

 

 

(18.3)

(23.9)

(29.4)

 

(35.0)

(40.6)

(46.1)

 

 

 

 

 

TC

24,430

23,750

23,010

 

22,310

18,420

11,170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

(22.2)

SHC

17,180

16,720

16,370

 

16,020

13,920

10,540

 

59

 

76 (24.4)

SHC

19,050

18,700

18,230

 

17,880

15,900

11,170

 

(15.0)

 

80

(26.7)

SHC

21,030

20,680

20,330

 

19,860

17,880

11,170

 

 

 

84

(28.9)

SHC

23,010

22,660

22,200

 

21,850

18,420

11,170

 

 

 

88

(31.1)

SHC

24,430

23,750

23,010

 

22,310

18,420

11,170

 

 

 

 

 

TC

25,360

24,690

23,940

 

23,260

18,810

11,390

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

(22.2)

SHC

14,730

14,380

13,920

 

13,690

11,590

8,320

 

63

 

76 (24.4)

SHC

16,600

16,250

15,900

 

15,550

13,450

10,300

 

(17.2)

 

80

(26.7)

SHC

18,580

18,230

17,880

 

17,530

15,430

11,390

 

 

 

84

(28.9)

SHC

20,560

20,210

19,860

 

19,510

17,420

11,390

 

 

 

88

(31.1)

SHC

22,430

22,080

21,730

 

21,380

18,810

11,390

 

 

 

 

 

TC

26,250

25,590

24,850

 

#

24,200

19,150

11,590

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

(22.2)

SHC

12,170

11,820

11,590

 

11,240

9,020

6,110

 

67

 

76

(24.4)

SHC

14,150

13,800

13,450

 

13,220

11,000

8,090

 

(19.4)

 

80

(26.7)

SHC

16,130

15,780

15,430

 

15,200

12,990

10,070

 

 

 

84

(28.9)

SHC

18,000

17,770

17,420

 

17,070

14,970

11,590

 

 

 

88

(31.1)

SHC

19,980

19,630

19,280

 

19,050

16,830

11,590

 

 

 

 

 

TC

27,080

26,430

25,700

 

25,100

19,420

11,740

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

(22.2)

SHC

9,490

9,260

8,910

 

8,670

6,460

3,780

 

71

 

76

(24.4)

SHC

11,470

11,120

10,890

 

10,650

8,440

5,760

 

(21.7)

 

80

(26.7)

SHC

13,450

13,220

12,870

 

12,640

10,420

7,740

 

 

 

84

(28.9)

SHC

15,320

15,080

14,730

 

14,500

12,290

9,720

 

 

 

88

(31.1)

SHC

17,300

17,070

16,720

 

16,480

14,270

11,590

 

 

 

 

 

TC

27,740

27,120

26,410

 

25,850

19,570

11,830

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

76

(24.4)

SHC

8,790

8,560

8,320

 

8,090

5,870

3,540

 

(23.9)

 

80

(26.7)

SHC

10,770

10,540

10,300

 

10,070

7,970

5,520

 

 

 

84

(28.9)

SHC

12,750

12,520

12,290

 

12,050

9,840

7,390

 

 

 

88

(31.1)

SHC

14,620

14,380

14,150

 

13,920

11,820

9,370

 

 

 

 

 

TC : Total

Cooling

Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.

:Outdoor Ambient Temp. 95 °F (35 °C) D.B.

2.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.

3.Above data represents the value when the operation frequency of a compressor is fixed.

24

Page 24
Image 24
Sanyo CH2472, CH1872 service manual 24,200 BTU/h