4.4 Special functions list - SF

4.4.17Threshold trigger

Short description

The output is set and reset with two configurable threshold triggers.

Symbol in LOGO!

Wiring

Description

 

 

Input Fre

The function counts the 0 to 1 transitions at input Fre.

)UH

 

 

1 to 0 transitions are not counted.

4

 

Use

3DU

 

 

 

 

 

 

inputs I3, I4, I5, I6 for fast counting (only LOGO!

 

 

 

12/24RC/RCo, LOGO! 12/24RCE, LOGO! 24/24o

 

 

 

and LOGO! 24C/24Co): max. 5 kHz, if the fast

 

 

 

input is directly connected to the threshold trigger

 

 

 

function block

 

 

 

any other input or circuit component for counting

 

 

 

low frequency signals (typ. 4 Hz).

 

 

 

 

 

 

Parameter

On: On threshold

 

 

 

Range of values:

 

 

 

0000...9999

 

 

 

Off: Off threshold

 

 

 

Range of values:

 

 

 

0000...9999

 

 

 

G_T: Time interval or gate time during which the input

 

 

 

pulses are measured.

 

 

 

Range of values:

 

 

 

00:00 s...99:99 s

 

 

Output Q

Q is set and reset at the thresholds.

Parameter G_T

The gate time G_T can be provided by the actual value of another already-programmed function. You can use the actual values of the following functions:

Analog comparator (Page 218) (actual value Ax – Ay)

Analog threshold trigger (Page 213) (actual value Ax)

Analog amplifier (Page 226) (actual value Ax)

Analog multiplexer (Page 248) (actual value AQ)

Analog ramp (Page 251) (actual value AQ)

Mathematic instruction (Page 265) (actual value AQ)

PI controller (Page 256) (actual value AQ)

Up/down counter (Page 201) (actual value Cnt)

 