LOGO! functions

4.4 Special functions list - SF

Timing diagram B: Function with positive difference Δ

2II 2Q˂

2Q

$[

4

Functional description

The function fetches the analog signal at input Ax.

Ax is multiplied by the value of the A (gain) parameter, and the value at parameter B (offset) is added to product, i.e. (Ax • gain) + offset = actual value of Ax.

Output Q is set or reset, depending on the set (On) threshold and difference value (Δ). The function automatically calculates the Off parameter: Off = On + Δ, whereby Δ may be positive or negative. See the calculation rule below.

Calculation rule

When you set a negative differential value Δ, the On threshold ≥ Off threshold, and: Q = 1, if the actual value Ax > On

Q = 0, if the actual value Ax ≤ Off. See the timing diagram A.

When you set a positive differential value Δ, the On threshold < the Off threshold, and Q = 1, if:

On ≤ actual value Ax < Off.

See the timing diagram B.

Setting the Par parameter

The gain and offset parameters are used to adapt the sensors to the relevant application. View in programming mode (example):

% 2Q  ෙ 

Press

% $  %  S 

3DUDPHWHUSURWHFWLRQPRGH

2QRIIWKUHVKROG

'LIIHUHQWLDOYDOXHIRUWKHRQRII

WKUHVKROG

*DLQ

2IIVHW

'HFLPDOVLQWKHPHVVDJHWH[W

LOGO!

 

Manual, 04/2011, A5E03556174-01

217