I/O Connections 9300 Series User’s Guide
Page 156 Chapter 7 - Hardware Reference
Analog Outputs
This ordering option provides four analog outputs. Two varieties are available:
NOTE
There is one common terminal for all of the Analog Outputs.
Specification 0-20 mA (scalable to
4-20 mA) Option 0-1 mA Option
Max. Load Drive Capability 500 10 k
Accuracy ±0.3% of full-scale
Outputs A1, A2, A3, A4
Connectors Phoenix captured-wire
Channel to Channel
Isolation None
Max. Common Mode
Voltage 30 V
Standards Compliance IEC 61000-4-4 fast transient test with capacitive clamp (4 kVp-
p@2.5 kHz for 1 min)
ANALOGINPUT PORTS
+AI1 -

+

_

Analog Source

(Voltage/ Current) In

Out