9300 Series User’s Guide Using the Modbus RTU Protocol
Chapter 3 - Default Meter Functionality Page 57
Modbus Slave Module #2 LinksModbus Slave Module #3 Links
Average L-L Voltage Vll avg Power Meter Modbus Slave #1 – Source Input #8 40018
Phase A Current I a Power Meter Modbus Slave #1 – Source Input #9 40019
Phase B Current I b Power Meter Modbus Slave #1 – Source Input #10 40020
Phase C Current I c Power Meter Modbus Slave #1 – Source Input #11 40021
Average Current I avg Power Meter Modbus Slave #1 – Source Input #12 40022
Voltage Unbalance V unbal Power Meter Modbus Slave #1 – Source Input #13 40023
Current Unbalance I unbal Power Meter Modbus Slave #1 – Source Input #14 40024
Line Frequency Freq Power Meter Modbus Slave #1 – Source Input #15 40025
L-N Voltage Phase A Vln a Power Meter Modbus Slave #1 – Source Input #1 40011
Measurement Label Source ION Module Modbus Module and Input Number Modbus Register
Measurement Label Source ION Module Modbus Module and Input Number Modbus Register
Phase A kW kW a Power Meter Modbus Slave #2 – Source Input #1 40027-40028
Phase B kW kW b Power Meter Modbus Slave #2 – Source Input #2 40029-40030
Phase C kW kW c Power Meter Modbus Slave #2 – Source Input #3 40031-40032
Total kW kW tot Power Meter Modbus Slave #2 – Source Input #4 40033-40034
Phase A kVAR kVAR a Power Meter Modbus Slave #2 – Source Input #5 40035-40036
Phase B kVAR kVAR b Power Meter Modbus Slave #2 – Source Input #6 40037-40038
Phase C kVAR kVAR c Power Meter Modbus Slave #2 – Source Input #7 40039-40040
Total kVAR kVAR tot Power Meter Modbus Slave #2 – Source Input #8 40041-40042
Phase A kVA kVA a Power Meter Modbus Slave #2 – Source Input #9 40043-40044
Phase B kVA kVA b Power Meter Modbus Slave #2 – Source Input #10 40045-40046
Phase V kVA kVA c Power Meter Modbus Slave #2 – Source Input #11 40047-40048
Total kVA kVA tot Power Meter Modbus Slave #2 – Source Input #12 40049-40050
Phase A signed PF PF sig n a Power Meter Modbus Slave #2 – Source Input #13 40051-40052
Phase B signed PF PF sign b Power Meter Modbus Slave #2 – Source Input #14 40053-40054
Phase C signed PF PF sign c Power Meter Modbus Slave #2 – Source Input #15 40055-40056
Measurement Label Source ION Module Modbus Module and Input Number Modbus Register
kW Thermal Dmd kW td Thermal Demand Modbus Slave #3 – Source Input #1 40059-40060
kVAR Thermal Dmd kVAR td Thermal Demand Modbus Slave #3 – Source Input #2 40061-40062
kVA Thermal Dmd kVA td Thermal Demand Modbus Slave #3 – Source Input #3 40063-40064
Max kW Th Dmd kW td mx Maximum Modbus Slave #3 – Source Input #4 40065-40066